G
uidance
−16−
STEP 4
Set the parameters of
CRD-KD
Set the parameters of the
CRD-KD
using any of the
OPX-2A
,
MEXE02
, RS-485 communication or
MECHATROLINK-
Ⅲ
communication.
1. Set the "START input mode (1C00h)" parameter of the
CRD-KD
to "0: RS-485 communication."
(Initial setting: I/O)
2. Set the position (travel amount: 1001h) and operating speed (1101h) to the operation data No.1 of the
CRK-KD
.
3.
Set the "Data No. input mode (1C0Dh)" parameter of the
CRD-KD
to "0: RS-485 communication."
(Initial setting: I/O)
4. Set the "STOP contact configuration (1C03h)" parameter of the
CRD-KD
to "0: Normally open."
(Initial setting: Normally closed)
Note
•
Operation data or parameters set via RS-485 communication or MECHATROLINK-
Ⅲ
communication
will be written to the RAM of the
CRD-KD
. The data stored in the RAM will be erased when turning
off the power supply of the
CRD-KD
. When saving the data to the non-volatile memory, execute the
"batch NV memory write" command of the maintenance command.
•
The operation data or parameters set by the
OPX-2A
or
MEXE02
will be saved to the non-volatile
memory of the
CRD-KD
.
•
The non-volatile memory can be rewritten approx. 100,000 times.
STEP 5
Execute positioning operation
Control the I/O signal of the
CRD-KD
using the standard I/O command (DATA_RWA: 20h) of
MECHATROLINK-
Ⅲ
communication.
1. Select the data No.1 by turning the M0 of the address number 0.
2. Execute positioning operation by turning the START of the address number 0 to ON.
STEP 6
Were you able to operate the motor properly?
How did it go? Were you able to operate the motor properly? If the motor does not function, check the
following points:
•
Is any alarm present in the
NETC01-M3
or
CRD-KD
?
•
Are the address number, transmission rate and termination resistor set correctly?
•
Are the "connection" parameters of the
NETC01-M3
set correctly?
•
Is the C-ERR LED lit? (RS-485 communication error)
•
Is the ERR LED lit? (MECHATROLINK-
Ⅲ
communication error)
•
Is the operation data set correctly?
•
Is the motor for the
CRD-KD
excited? Or is the excitation setting correct?
•
Are the
CRD-KD
parameters set correctly?
•
Is the STOP input of the
CRD-KD
I/O turned ON?
For more detailed settings and functions, refer to the following pages.