Setting
−17−
7 Setting
This chapter explains how to set the functions of the
NETC01-M3
.
Operation mode setting switch
(SW2-Nos.1 to 3)
MECHATROLINK-
䊢
station
number setting switches
(STATION No.×1, ×10)
RS-485 communication
transmission rate setting
switch (SW1)
Note
Be sure to turn off the
NETC01-M3
power before setting the switches. If the switches are set while
the power is still on, the new switch settings will not become effective until the
NETC01-M3
power is
cycled.
7.1 Transmission rate of RS-485 communication
Set the transmission rate using the transmission rate setting switch (SW1).
Factory setting 7 (625 kbps)
Note
•
For the SW1, always set to "7." If the switch is set to the dial of "8" or higher, the communication switch
setting error alarm will be generated when turning on the power. And do not set the switch to the dial
of "0" to "6" because they cannot be used. (An alarm will not be generated.)
•
For the transmission rate of the RS-485 communication compatible product, set to 625 kbps.
7.2 Operation mode
Set the remote I/O occupied size and number of transmission bytes for the RS-485 communication
compatible product connecting to a
NETC01-M3
. Set the remote I/O occupied size using the operation
mode setting switch SW2-No.1, and set the number of transmission bytes using the SW2-No.2 and No.3.
If the operation mode is changed, cycle the power.
Factory setting No.1: OFF (Remote I/O occupied size: 16 bit mode)
No.2: OFF, No.3: ON (Number of transmission bytes: 32 bytes)
SW2
Description
Factory setting
No.1
Sets the remote I/O occupied size.
OFF: 16 bit mode (Up to 8 units can be connected)
ON: 8 bit mode (Up to 16 units can be connected)
OFF
No.2
No.3
Sets the number of transmission bytes.
No.2=OFF, No.3=OFF: 16 bytes
No.2=OFF, No.3=ON: 32 bytes
No.2=ON, No.3=OFF: 48 bytes
No.2=ON, No.3=ON: 64 bytes
No.2: OFF
No.3: ON
Note
The SW2-No.4 is not used.