S P E C I A L F U N C T I O N S
116 / 216
XS10000_manual_ger_eng_it_V1.1.2.doc
R. Kistler
5.1.2
Commissioning redundant/increase mode
NOTE
HE mode is not available, please disable
Additional settings must not be made
This chapter discusses the main features of the increase
mode and additionally refers to the
Commissioning
section
1. Connect the load (consumers) to the UPS systems without
switching on the load.
2. If there is a maintenance switch installed, switch this to UPS
mode now.
3. Switch the power supply on.
The LCD display on the front covers of the UPS systems lights
up and displays the ONLINE logo.
4. Check whether the UPS systems are in the bypass mode (see
Operating states
).
5. Press the
button on one of the UPS systems for at least
one second. All UPS systems switch to normal mode.
6. If the display of one of the UPS systems displays active warn-
ing/error messages, rectify these problems before you pro-
ceed with commissioning the system (see
Troubleshooting
).
7. Check whether the UPS systems generate the same output
voltage. The output voltages may deviate by a maximum of
0.5 V. Otherwise, make the appropriate setting (see
Settings
menu
).
8. Switch on the output switches of the UPS systems and then
switch on the main output switch. The UPS systems are now
working in redundant/increase mode.
9. Switch the load on and check whether the connected load is
supplied.
Содержание XANTO S 10000
Страница 2: ...2 216 XS6000 XS10000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 70: ...T E C H N I S C H E D A T E N 70 216 XS6000 XS10000_manual_ger_eng_it_V1 1 2 doc R Kistler 9 3 CE Bestätigung ...
Страница 72: ...72 216 XS6000 XS10000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 74: ...74 216 XS6000 XS10000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 142: ...T E C H N I C A L D A T A 142 216 XS6000 XS10000_manual_ger_eng_it_V1 1 2 doc R Kistler 9 3 CE conformity ...
Страница 144: ...144 216 XS6000 XS10000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 146: ...146 216 XS6000 XS10000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Страница 214: ...D A T I T E C N I C I 214 216 XS6000 XS10000_manual_ger_eng_it_V1 1 2 doc R Kistler 9 3 Dichiarazione CE ...
Страница 216: ...216 216 XS6000 XS10000_manual_ger_eng_it_V1 1 2 doc R Kistler ...