I N S T A L L A T I O N
98 / 216
XS10000_manual_ger_eng_it_V1.1.2.doc
R. Kistler
10. If an additional emergency-off switch was installed, the emer-
gency-off function must also be checked:
To check this, operate the emergency-off switch and check
that the status switches on the display of the UPS system.
Deactivate the emergency-off switch and restart the UPS
system.
NOTE
The internal batteries will charge up to 90% of their capacity
in less than three hours. ONLINE recommends charging the
batteries for 48 hours after installation or after a longer peri-
od of storage. If additional battery modules were installed,
please refer to the charging times in the
Technical Data
chapter.