10-32
Param-
eter
No.
Regis-
ter No.
(Hex)
Name
Description
Set-
ting
range
Unit
of
set-
ting
Default
setting
Changes
during
opera-
tion
Ref-
er-
ence
page
n168
01A6
Output open-
phase detec-
tion level
(See note 1.)
Sets as a percentage the current for
detecting an output open phase, tak-
ing the Inverter’s rated output current
as 100%.
If “0” is set, the output open-phase
detection function will be disabled.
Recommended setting: 5 (%)
0 to
100
1 %
0
No
6-47
n169
01A6
Output open-
phase detec-
tion time (See
note 1.)
Sets the output open-phase detection
time in units of seconds.
If “0” is set, the output open-phase
detection function will be disabled.
Recommended setting: 0.2 (s)
0.0 to
2.0
0.1 s
0.0
No
6-47
n170
01AA
Enter Com-
mand Opera-
tion Selection
Select the treatment of the Enter
command for momentay power inter-
ruptions.
0: Accept Enter command only when
operation is stopped.
1: Accept Enter command at any
time.
* Changed parameters are enabled
even if the Enter command is not
sent, but the changes will be lost if
power is reset if the Enter com-
mand has not been sent.
0 to 1
1
0
No
7-18
n171
---
Not used
---
---
---
---
---
---
n172
n173
01AD
Proportional
Gain for DC
Control
Normally use this parameter at the
default setting.
1 to
999
1
(0.001)
83
(0.083)
10 (See
note 2.)
No
---
n174
01AE
Integral Time
Constant for
DC Control
Normally use this parameter at the
default setting.
1 to
250
1
(4 ms)
0
(100 ms)
10 (See
note 2.)
No
---
Note 1.
Available for 5.5-kW and 7.5-kW Inverters only.
Note 2.
These parameters are available on 200-V/400-V, 4.0-kW (or less) Inverters (software version
VSP010024 or higher) or 5.5-kW/7.5-kW Inverters (VSP010104 or higher).
List of Parameters
Chapter 10
Содержание SYSDRIVE 3G3MV-A2001
Страница 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Страница 2: ......
Страница 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Страница 18: ......
Страница 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Страница 32: ......
Страница 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 74: ......
Страница 75: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 102: ......
Страница 142: ......
Страница 242: ......
Страница 268: ......
Страница 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 293: ...9 25 D 3G3MV PRS2030V PRS3020V Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 294: ...9 26 D 3G3MV PRS2050V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 297: ...9 29 D 3G3MV PRS1040V Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 303: ...Chapter 10 List of Parameters 10...
Страница 337: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 343: ......
Страница 344: ...I527 E1 04...