10-30
Param-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of
set-
ting
Set-
ting
range
Description
Name
Regis-
ter No.
(Hex)
n157
019D
RS-422/485
RTS control
selection
Select whether or not to enable the
RTS (request-to-send) communica-
tions control function.
0: RTS control enabled
1: RTS control disabled (available to
1-to-1 RS-422 communications
only)
0, 1
1
0
No
7-5
n158
019E
Motor code
Sets the code to automatically set the
constants for energy-saving control.
0 to 10: 200-V AC, 0.1- to 4.0-kW
motor
20 to 30: 400-V AC, 0.1- to 4.0-kW
motor
0 to 70
1
Varies
with the
capac-
ity.
No
6-6
n159
019F
Energy-sav-
ing voltage
upper limit at
60-Hz output
These parameters prevent the motor
from over excitation due to voltage
changes during energy-saving con-
trol.
Sets the upper limit of output voltage
0 to
120
1%
120
No
6-8
n160
01A0
Energy-sav-
ing upper
limit voltage
at 6-Hz out-
put
Sets the upper limit of output voltage
as a percentage at each frequency
based on the rated motor voltage as
100%.
* Normally, the default settings do
not need to be changed.
0 to 25
1%
16
No
6-8
n161
01A1
Power detec-
tion width for
probe opera-
tion switching
Sets the detection width of power that
sets the Inverter into probe operation.
Sets the width as a percentage based
on the power to be detected as 100%.
* Normally, the default setting does
not need to be changed.
* The Inverter will operate with a
power detection width of 10% if the
value is set to 0.
0 to
100
1%
10
No
6-10
n162
01A2
Power detec-
tion filter con-
stant
Sets the filter time constant of the
power detection block of the Inverter
operating in probe operation.
Filter time constant (ms) = Set value
in n162 x 4 (ms)
* Normally, the default setting does
not need to be changed.
* The Inverter will operate with a
time constant of 20 ms if the value
is set to 0.
0 to
255
1 (4
ms)
5
No
6-10
n163
01A3
PID output
gain
Sets the rate by which PID control
value is multiplied for PID control.
* Normally, the default setting does
not need to be changed.
0.0 to
25.0
0.1
1.0
No
6-18
List of Parameters
Chapter 10
Содержание SYSDRIVE 3G3MV-A2001
Страница 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Страница 2: ......
Страница 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Страница 18: ......
Страница 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Страница 32: ......
Страница 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 74: ......
Страница 75: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 102: ......
Страница 142: ......
Страница 242: ......
Страница 268: ......
Страница 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 293: ...9 25 D 3G3MV PRS2030V PRS3020V Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 294: ...9 26 D 3G3MV PRS2050V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 297: ...9 29 D 3G3MV PRS1040V Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 303: ...Chapter 10 List of Parameters 10...
Страница 337: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 343: ......
Страница 344: ...I527 E1 04...