3-16
Note 3.
The following parameter set values cannot be copied if the Inverters are different to each
other in capacity.
n011 to n017: V/f setting
n108: Motor leakage inductance
n036: Rated motor current
n109: Torque compensation limit
n080: Carrier frequency
n110: Motor no-load current
n105: Torque compensation core loss
n140: Energy-saving control coefficient K2
n106: Rated motor slip
n158: Motor code
n107: Motor wire-to-wire resistance
Note 4.
Functions for 5.5-/7.5-kW Inverters cannot be copied to Inverters with different capacities.
H
Verifying the Parameter Set Values (vFy)
•
In order to verify that the copied parameter set values in the Inverter coincide with those in the
EEPROM of the Digital Operator, set n176 for parameter copy function selection to vFy.
Note
The parameter set values can be verified provided that they are copied between the Inverters that
are the same in power supply specification and control mode (i.e., V/f or vector control).
D
Procedure to Verify the Parameter Set Values
Key sequence
Indicator
Display
example
Explanation
Power ON
Press the Mode Key repeatedly until the PRGM
indicator is lit.
Use the Increment or Decrement Key to display
“n176.”
Press the Enter Key. Then “rdy” will be displayed.
Use the Increment Key to display “vFy.”
Press the Enter Key so that the parameter set values
are verified, during which the display flashes.
If there is a parameter set value that does not coincide,
the parameter number will flash.
Press the Enter Key so that the corresponding set
value in the Inverter will flash.
Press the Enter Key again so that the corresponding
set value in the EEPROM of the Digital Operator will
flash.
Press the Increment Key so that verification will
resume.
Completes
When the set values have been all checked, “End” will
be displayed.
or
Press the Mode or Enter Key. The parameter number
(n176) will be displayed again.
Note 1.
The above operation is interrupted when the STOP/RESET Key is pressed while the parame-
ter number or parameter set value is flashing because the parameter set value does not coin-
cide. “End” will be displayed. By pressing the Mode or Enter Key, the parameter number
(n176) is displayed again.
Preparing for Operation and Monitoring
Chapter 3
Содержание SYSDRIVE 3G3MV-A2001
Страница 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Страница 2: ......
Страница 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Страница 18: ......
Страница 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Страница 32: ......
Страница 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 74: ......
Страница 75: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 102: ......
Страница 142: ......
Страница 242: ......
Страница 268: ......
Страница 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 293: ...9 25 D 3G3MV PRS2030V PRS3020V Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 294: ...9 26 D 3G3MV PRS2050V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 297: ...9 29 D 3G3MV PRS1040V Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 303: ...Chapter 10 List of Parameters 10...
Страница 337: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 343: ......
Страница 344: ...I527 E1 04...