6-33
Set Values
Setting
Description
0
Inverter does not monitor undertorque.
1
Inverter monitors undertorque only while matching speed. It continues operation (warning)
even after undertorque is detected.
2
Inverter monitors undertorque only while matching speed. It discontinues operation
(protective operation) when undertorque is detected.
3
Inverter monitors undertorque during operation. It continues operation (warning)
even after undertorque is detected.
4
Inverter monitors undertorque during operation. It discontinues operation
(protective operation) when undertorque is detected.
•
Set n117 (undertorque detection function selection, n118 (undertorque detection level) and n119 (un-
dertorque detection time) to enable the undertorque detection function. The Inverter will detect under-
torque when current (or torque) the same as or lower than the detection level is output for the preset
detection time.
•
Set a multi-function input (n057 to n059) to output an undertorque detection signal to an external de-
vice.
Set value: 8 for undertorque detection (NO-contact input)
Set value: 9 for undertorque detection (NC-contact input)
Undertorque detection
Undertorque detection
level (n118)
Frequency matching
Undertorque being
detected (NO con-
tact)
n119
Undertorque detection time
Time
Note
Undertorque detection will be canceled if the value increases from the detection level by approxi-
mately 5% of the Inverter rated current (or motor’s rated torque).
n118
Undertorque detection level
Register
0176 Hex
Changes during
operation
No
Setting
range
0 to 200
Unit of
setting
1%
Default setting
10%
Set Values
•
Set the undertorque detection level.
To detect the level through the output torque, set the torque in a percentage based on the motor’s rated
torque as 100%.
To detect the level through the output current, set the current in percentage based on the rated current
of the Inverter as 100%.
Note
With general-purpose motors, for example, a current equivalent to approx. 60% of the motor’s
rated current will be generated when there is no load. (This current will vary according to the type
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3MV-A2001
Страница 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Страница 2: ......
Страница 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Страница 18: ......
Страница 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Страница 32: ......
Страница 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 74: ......
Страница 75: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 102: ......
Страница 142: ......
Страница 242: ......
Страница 268: ......
Страница 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 293: ...9 25 D 3G3MV PRS2030V PRS3020V Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 294: ...9 26 D 3G3MV PRS2050V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 297: ...9 29 D 3G3MV PRS1040V Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 303: ...Chapter 10 List of Parameters 10...
Страница 337: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 343: ......
Страница 344: ...I527 E1 04...