4-7
Key sequence
Indicator
Display
example
Explanation
The parameter number is displayed.
Use the Increment or Decrement Key to display “n002.”
Press the Enter Key to display the set value in n002.
Use the Increment or Decrement key to set n002 to 0
unless the value is already set to 0, during which the
display flashes.
Press the Enter Key so that the set value will be entered
and the data display will be lit.
In approximately
1 s.
The parameter number will be displayed again in
approximately 1 s.
H
Setting the Rated Motor Current
Parame-
ter
Register
Name
Description
Setting
range
Unit of
setting
Default
setting
Chan-
ges dur-
ing
opera-
tion
n036
0124
Rated
motor
current
Used to set the rated motor
current (A) used for the ref-
erence current of motor
overload detection (OL1).
Note
1.
The default set-
ting for the rated
motor current is
the standard rated
current of the
maximum applica-
ble motor.
Note
2.
Motor overload
detection (OL1) is
disabled by set-
ting the parameter
to 0.0.
0.0% to
150%
(A) of
rated
output
current
of the
Inverter
0.1 A
See note
1 under
“Descrip-
tion.”)
No
Key sequence
Indicator
Display
example
Explanation
The parameter number is displayed.
Use the Increment or Decrement Key to display “n036.”
Press the Enter Key to display the set value in n036.
Use the Increment or Decrement Key to set n036 to the
rated motor current, during which the display flashes.
Press the Enter Key so that the set value will be entered
and the data display will be lit.
In approximately
1 s.
The parameter number will be displayed again in
approximately 1 s.
Test Run
Chapter 4
Содержание SYSDRIVE 3G3MV-A2001
Страница 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Страница 2: ......
Страница 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Страница 18: ......
Страница 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Страница 32: ......
Страница 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 74: ......
Страница 75: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 102: ......
Страница 142: ......
Страница 242: ......
Страница 268: ......
Страница 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 293: ...9 25 D 3G3MV PRS2030V PRS3020V Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 294: ...9 26 D 3G3MV PRS2050V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 297: ...9 29 D 3G3MV PRS1040V Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 303: ...Chapter 10 List of Parameters 10...
Страница 337: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 343: ......
Страница 344: ...I527 E1 04...