10-29
Param-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of
set-
ting
Set-
ting
range
Description
Name
Regis-
ter No.
(Hex)
n151
0197
RS-422/485
communica-
tions time-
over detec-
tion selection
The set value in the parameter deter-
mines whether communications time-
over detection will be performed with
“CE” displayed if there is an interval
of more than 2 s between normal
communications and how the
detected communications time-over
will be processed.
0: Detects time-over, fatal error, and
the Inverter coasts to a stop.
1: Detects time-over, detects fatal
error, and the Inverter decelerates
to a stop in deceleration time 1.
2: Detects time-over, detects fatal
error, and the Inverter decelerates
to a stop in deceleration time 2.
3: Detects time-over, detects nonfatal
error warning, and the Inverter
continues operating.
4: No time-over is detected.
0 to 4
1
0
No
7-2
n152
0198
RS-422/485
communica-
tions fre-
quency refer-
ence/display
unit selection
Sets the unit of frequency reference
and frequency-related values to be
set or monitored through communica-
tions.
0: 0.1 Hz
1: 0.01 Hz
2: Converted value based on 30,000
as max. frequency
3: 0.1% (Max. frequency: 100%)
0 to 3
1
0
No
7-3
n153
0199
RS-422/485
communica-
tions Slave
address
Set this parameter to the Slave
address (Slave unit number) for com-
munications.
00: Broadcast message (with the
communications function disabled)
01 to 32: Slave address
00 to
32
1
00
No
7-3
n154
019A
RS-422/485
baud rate
selection
Select the communications baud rate.
0: 2,400 bps
1: 4,800 bps
2: 9,600 bps
3: 19,200 bps
0 to 3
1
2
No
7-4
n155
019B
RS-422/485
parity selec-
tion
Select the parity check function for
communications data.
0: Even
1: Odd
2: No parity
0 to 2
1
0
No
7-4
n156
019C
RS-422/485
send wait
time
Sets the time to wait for a response
after the DSR (data-send-request)
message is received from the Master.
10 to
65
1 ms
10
No
7-4
List of Parameters
Chapter 10
Содержание SYSDRIVE 3G3MV-A2001
Страница 1: ...Cat No I527 E1 04 USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter...
Страница 2: ......
Страница 3: ...USER S MANUAL Multi function Compact Inverter SYSDRIVE 3G3MVSERIES...
Страница 18: ......
Страница 23: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature 1 3 New Features 1...
Страница 32: ......
Страница 33: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 74: ......
Страница 75: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 93: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 102: ......
Страница 142: ......
Страница 242: ......
Страница 268: ......
Страница 269: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 293: ...9 25 D 3G3MV PRS2030V PRS3020V Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 294: ...9 26 D 3G3MV PRS2050V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 297: ...9 29 D 3G3MV PRS1040V Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 303: ...Chapter 10 List of Parameters 10...
Страница 337: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 343: ......
Страница 344: ...I527 E1 04...