7 GRT1-ECT Installation
7 - 16
GX-series EtherCAT Slave Unit User’s Manual
Removing Wires
To remove the wires press the release button above the terminal hole using a slotted precision
screwdriver and pull out the wire.
Recommended Power Supplies
Use a SELV power supply with over current protection.
A SELV power supply has redundant or increased insulation between the I/O, an output voltage of
30 Vr.m.s and a 42.4-V peak or maximum of 60 VDC.
Recommended power supply: S82K-01524 (OMRON) or S8TS-06024 (OMRON).
Recommended Wire
Strip Length
Pin Terminal Length
Strip wire between 7 and 10 mm of insulation at the ends of the wires (stranded or solid wire) or use
pin terminals with a pin (conductor) length of 8 to 10 mm.
Type
Gauge
Stranded wire
20 AWG to 16 AWG
(0.5 to 1.25 mm
2
)
Solid wire
Pin terminal
Slotted precision screwdriver
Release button
3.5 mm
0.6 mm
Side view
Front view
Recommended model: SZF1 (Phoenix Contact)
Strip 7 to 10 mm.
Pin length: 8 to 10 mm
Содержание GRT1-ECT SmartSlice
Страница 3: ...GRT1 series EtherCAT Communication Unit Operation Manual Revised March 2012 ...
Страница 18: ...15 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 30: ...1 EtherCAT Network 1 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 38: ...2 EtherCAT Communication details 2 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 52: ...4 GRT1 ECT Details 4 10 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 76: ...6 GRT1 ECT Troubleshooting 6 12 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 136: ...A4 Appendix Object Dictionary A4 16 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 140: ...Revision 2 GRT1 ECT series EtherCAT Slave Unit User s Manual ...