5 GRT1-ECT Procedures
5 - 4
GRT1-series EtherCAT Communication Unit - Operation Manual
Reference
•
The presence of Turnback units and cables does not influence the automatic allocation of Unit
numbers.
•
The unit numbers allocated automatically to the SmartSlice I/O Units are unrelated to the
EtherCAT station address set with the rotary switches.
These flags can be used to monitor the status of the connections between the GRT1-ECT and the
SmartSlice I/O Units as well as the status of the SmartSlice I/O Units themselves. The status flags
take up 1 word and the information is transferred to the Master as part of the Input data. The table
below defines the individual bits in the Status word.
5-2-4
Communication Unit’s Status Flags
Bit
Name
Contents
0
SmartSlice I/O Bus
Communication Error
Monitors the status of SmartSlice I/O communication
1
-
Reserved
2
SmartSlice I/O Unit Warning
0: Normal
1: Error detected
Indicates a minor SmartSlice I/O Unit error.
This flag goes ON when there is an error in any one of
the connected SmartSlice I/OUnits
3
-
Reserved
4
SmartSlice I/O Unit Alarm
0: Normal
1: Error detected
Indicates a major SmartSlice I/O Unit error.
This flag goes ON when there is an error in one of the
connected SmartSlice I/O Units
5-11
-
Reserved
12
Unit Maintenance
0: Normal
1: Error (monitor value reached)
Monitors the operating time threshold that is set with
the Unit power ON time monitor function
13
Automatic Restore Monitor
0: Restore successful
1: Restore failed
Indicates whether or not the automatic parameter
restore to the SmartSlice I/O Units was completed
successfully
14
Communication Unit Error
0: Normal
1: Error occurred
This flag is ON if one of the other flags (bits 0 to 13) is
ON
15
I/O Refreshing
0: I/O communication stopped
1: I/O communication normal
Indicates whether I/O data is exchanged normally
EtherCAT
Communication Unit
The SmartSlice I/O unit numbers are assigned
automatically in order, from left to right.
I/O
#1
I/O
#2
I/O
#3
I/O
#4
I/O
#64
:
:
Содержание GRT1-ECT SmartSlice
Страница 3: ...GRT1 series EtherCAT Communication Unit Operation Manual Revised March 2012 ...
Страница 18: ...15 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 30: ...1 EtherCAT Network 1 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 38: ...2 EtherCAT Communication details 2 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 52: ...4 GRT1 ECT Details 4 10 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 76: ...6 GRT1 ECT Troubleshooting 6 12 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 136: ...A4 Appendix Object Dictionary A4 16 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 140: ...Revision 2 GRT1 ECT series EtherCAT Slave Unit User s Manual ...