6 GRT1-ECT Troubleshooting
6 - 8
GRT1-series EtherCAT Communication Unit - Operation Manual
Due to the EtherCAT specification, a communication timeout does not occur with those Slaves that only handle
input data.
Errors returning AL status code
−
SF
−
Safe-
Operational
state
It is commanded
from the EtherCAT
Master Unit to shift
to the Safe-Opera-
tional state.
If the undesired state occured during
operation of the system, check the
state of the connected EtherCAT
Master Unit.
−
B
−
Pre-
Operational
state
It is commanded
from the EtherCAT
Master Unit to shift
to the Pre-Opera-
tional state.
−
Off
−
Init state
It is commanded
from the EtherCAT
Master Unit to shift
to the Init state.
[L/A IN]
[L/A OUT]
indicator
[RUN]
indicator
[ERR]
indicator
Description
Cause
Actions
−
Off
B
AL status code
0x0061
ID-selector <> 0
and written Slave
Node Address <> 0
•
Slave Node Address is
automatically updated to 0
•
Cycle the power to the
GRT1-ECT
AL status code
0x8001
Unsupported
SmartSlice I/O Unit
detected
Remove the unsupported SmartSlice
I/O Unit. The following Units are not
supported:
•
GRT1-END-M: use GRT1-END
•
GRT1-CT1(-1) and -CP1-L are
supported from Ver.2.1
AL status code
0x8002
One or more
SmartSlice I/O
Units are not set to
their default config-
uration
Replace the SmartSlice I/O Unit(s) or
set to their default configuration.
AL status code
0x8003
Slice bus initializa-
tion failure
•
Slice registration wrong
•
Only an end-slice present
B
AL status code
0x0024
Input PDO map-
ping incorrect
Correct SmartSlice configuration
(Number or type of Digital or Analog
Input Units)
AL status code
0x0025
Output PDO map-
ping incorrect
•
Correct the output PDO mapping
according SmartSlice configura-
tion.
•
Correct SmartSlice configuration
(Number or type of Digital or Ana-
log Output Units)
[L/A IN]
[L/A OUT]
indicator
[RUN]
indicator
[ERR]
indicator
Description
Cause
Actions
Содержание GRT1-ECT SmartSlice
Страница 3: ...GRT1 series EtherCAT Communication Unit Operation Manual Revised March 2012 ...
Страница 18: ...15 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 30: ...1 EtherCAT Network 1 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 38: ...2 EtherCAT Communication details 2 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 52: ...4 GRT1 ECT Details 4 10 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 76: ...6 GRT1 ECT Troubleshooting 6 12 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 136: ...A4 Appendix Object Dictionary A4 16 GRT1 series EtherCAT Communication Unit Operation Manual ...
Страница 140: ...Revision 2 GRT1 ECT series EtherCAT Slave Unit User s Manual ...