22
Output Allocation, NX70 Pulse I/O unit (NX70-PULSE4)
- : No output allocation
[ ]
:
Indicate the connector pins on which the comparison results are directly output in
order to send to an external device. But the signal states are saved in the input
contacts, R1.0 to R1.7, so that you can monitor them with the programming software.
External
Terminal
Functions
Output
Counter
Comparison
Pulse
PWM
External
Terminal
[
II
]
A1
R2.0
-
[
Comparison CMP0
]
PLS0 direction
-
A2
R2.1
-
[
Comparison CMP1
]
PLS1 direction
-
A3
R2.2
-
[
Comparison CMP2
]
PLS2 direction
-
A4
R2.3
-
[
Comparison CMP3
]
PLS3 direction
-
A5
R2.4
-
[
Comparison CMP4
]
-
-
A6
R2.5
-
[
Comparison CMP5
]
-
-
A7
R2.6
-
[
Comparison CMP6
]
-
-
A8
R2.7
-
[
Comparison CMP7
]
-
-
B1
R2.8
-
-
[
PLS0 A
]
-
B2
R2.9
-
-
[
PLS0 B
]
-
B3
R2.10
-
-
[
PLS1 A
]
-
B4
R2.11
-
-
[
PLS1 B
]
-
B5
R2.12
-
-
[
PLS2 A
]
[
PWM0
]
B6
R2.13
-
-
[
PLS2 B
]
[
PWM1
]
B7
R2.14
-
-
[
PLS3 A
]
[
PWM2
]
B8
R2.15
-
-
[
PLS3 B
]
[
PWM3
]
Unit Internal
I/O
-
R3.0
CH0 Soft Clear
-
-
-
-
R3.1
CH0 Soft Mask
-
-
-
-
R3.2
CH1 Soft Clear
-
-
-
-
R3.3
CH1 Soft Mask
-
-
-
-
R3.4
CH2 Soft Clear
-
-
-
-
R3.5
CH2 Soft Mask
-
-
-
-
R3.6
CH3 Soft Clear
-
-
-
-
R3.7
CH3 Soft Mask
-
-
-
-
R3.8
-
-
PLS0 enabled
PWM0 enabled
-
R3.9
-
-
PLS1 enabled
PWM1 enabled
-
R3.10
-
-
PLS2 enabled
PWM2 enabled
-
R3.11
-
-
PLS3 enabled
PWM3 enabled
-
R3.12
-
-
PLS0 start
PWM0 start
-
R3.13
-
-
PLS1 start
PWM1 start
-
R3.14
-
-
PLS2 start
PWM2 start
-
R3.15
-
-
PLS3 start
PWM3 start
The I/O number allocations above are applied when NX70
PLC Pulse I/O unit (4CH) is installed in slot 0. I/O number can
differ depending on the installation slot.
ATTENTION