92
Function Specifications
(1)
This value applies when input time constant (filter) is set to N/A.
(2)
Pulse output and PWM output share a common CH.
When using combined functions, refer to the table below to select functions per
each CH.
Functions
Item
Description
Input, Output
Occupied I/O points
32 In/32 Out
External point
16 In/16 Out
Counter
Number of channels
4CH
Counting range
32-bit signed (-2,147,483,648 to +2,147,483,647)
Counting speed
200 kHz
(1)
Input mode
Direction control, individual input, phase input
Special functions
Multiplication (1, 2, 4)
Comparison
output
Point
Max. 8 points
Input time
constant
Point
16 points (2-point unit)
Constant
4, 8, 16, 32
µ
s
Pulse output
Number of channels
4CH
(2)
Cycle
1 Hz to 100 kHz (Set unit 1 Hz)
Output mode
Direction control, individual output
PWM output
Number of channels
4CH
(2)
Output current
Max. 0.8A/1CH
Duty
0 to 100% (Set unit 1%)
Cycle
1 Hz to 30 kHz (Set unit 1 Hz)
Combination
Using CH
CH0
CH1
CH2
CH3
1
PWM
PWM
PWM
PWM
2
PLS
PWM
PWM
PWM
3
PLS
PLS
PWM
PWM
4
PLS
PLS
PLS
PWM
5
PLS
PLS
PLS
PLS