32
Input Time Constant Functions
●
To use input time constant functions, shared memory setting is
needed.
Using Method
●
Set input constant for 8 external input terminal groups by setting
shared memory.
●
Input time constant is set for external output terminal, so function
allocations for each of input R0.0 to R0.15 settings are also valid.
(Counter input)
Input Time Constant Setting
(1)
Do not use this setting.
(2)
Initial value on power input is set to unused.
Input constant functions can be used along with counter
function.
IMPORTANT
b31~
b28
b27~
b24
b23~
b20
b19~
b16
b15~
b12
b11~
b8
b7~
b4
b3~
b0
Input time constant settings for R0.0 and R0.1
Input time constant settings for R0.2 and R0.3
Input time constant settings for R0.4 and R0.5
Input time constant settings for R0.6 and R0.7
Input time constant settings for R0.8 and R0.9
Input time constant settings for R0.10 and R0.11
Input time constant settings for R0.12 and R0.13
Input time constant settings for R0.14 and R0.15
Input time
constant
setting
Set value
(HEX)
Functions
Input time constant
Effective pulse width
0
Used
4
µ
s
1
8
µ
s
2
16
µ
s
3
32
µ
s
4
Invalid
(1)
Invalid
(1)
5
6
7
8
9
A
B
C
D
E
F
Unused
(2)
-