13
Pulse Output Function
●
Pulse I/O unit has 4CH for pulse output.
●
Max. 100 kHz output and 2 modes of output form as shown below
are available for pulse output function.
Output frequency can be set by 1 Hz unit.
●
Pulse output unit can be input to high-speed counter via internal
connection, providing high-speed processing.
PWM Output Function
●
Pulse I/O unit has 4CH for PWM output.
●
Max. 30 kHz is available for PWM output, and Duty can be set by
1% unit.
PLSx A
OFF
ON
PLSx B
OFF
ON
PLSx A
PLSx B
OFF
ON
OFF
ON
Forward dir)
Negative direction(-)
PLS0 A, PLS0 B
PLS1 A, PLS1 B
PLS2 A, PLS2 B
PLS3 A, PLS3 B
NX70 PLC
Pulse output unit
(NX70-PULSE4)
Direction control
CW-CCW
Forward dir) Negative direction(-)
NX70 PLC
Pulse output unit
(NX70-PULSE4)
PWM setting example
PWM 30%
off
on
PWM 60%
60%
40%
on
off
60%
30%
Max. 30 kHz
PWM3
PWM2
PWM1
PWM0
Pulse output and PWM output functions are only
available on pulse I/O unit.
ATTENTION