144
AC power line sizes
AC power line sizes
About AC power
feeds
Longer AC power feeds must be properly designed to preserve voltage levels to
the equipment. The wiring from the breaker panel to the power strip, which
supplies power to the R100 chassis and disk shelves, can often exceed 50 feet.
Note
Total AC wire length = breaker to wall or ceiling extension cable or
ceiling drop.
Recommended
conductor size
The following table lists the recommended conductor size for a 2% voltage drop
for a particular distance in feet (taken from the Radio Engineer’s Handbook).
Wire gauge
approximates
The following table lists the approximate equivalent of American Wire Gauge
(AWG) to Harmonized Cordage.
110V, single-phase
20A
circuit
30A
circuit
40A
circuit
50A
circuit
25 ft
12 AWG
10 AWG
8 AWG
8 AWG
50 ft
8 AWG
6 AWG
6 AWG
4 AWG
75 ft
6 AWG
4 AWG
4 AWG
2 AWG
220V, single-phase
20A
circuit
30A
circuit
40A
circuit
50A
circuit
25 ft
14 AWG
12 AWG
12 AWG
10 AWG
50 ft
12 AWG
10 AWG
8 AWG
8 AWG
75 ft
10 AWG
8 AWG
6 AWG
6 AWG
AWG
8
10
12
Harmonized, mm-mm
4.0
2.5
1.5
Содержание NearStore R100
Страница 6: ...vi Table of Contents...
Страница 20: ...10 Installation rules and restrictions...
Страница 54: ...44 Connecting an R100 chassis to an Ethernet network...
Страница 78: ...68 System messages at startup...
Страница 140: ...130 Replacing the CompactFlash unit subassembly...
Страница 164: ...154 Index...