Chapter 7: Replacing Internal Chassis Components
101
Installing an
expansion adapter
To install an expansion adapter, complete the following steps.
Step
Action
1
If you are...
Then...
Installing a new adapter
Take the adapter out of the
antistatic bag and discard the bag.
Installing a replacement
adapter
Take the replacement adapter out
of the antistatic bag and place the
used adapter into that bag.
2
If you are...
Then...
Replacing or reinstalling an
NVRAM III adapter
Plug the electrical wires from the
NVRAM battery to the connector
on the NVRAM III adapter. See
the figure in “
Replacing the
NVRAM III battery
” on page 104.
Reinstalling all other adapters
Go to Step 3.
3
Holding the adapter by its top edge, with the faceplate near the back
of the machine, lower the adapter into the slot until its connector edge
meets the grooves in the expansion slot.
The faceplate of the adapter should be in position against the back
panel, and should cover the endplate slot on the back panel.
4
Press carefully on the top edge of the adapter until the edge connector
is seated in the expansion slot.
5
Replace the faceplate screw to secure the adapter to the back panel.
6
Reconnect the cables to the external connectors on the replacement
expansion adapter.
7
Go to “
Closing the PCB carrier
” on page 110.
Содержание NearStore R100
Страница 6: ...vi Table of Contents...
Страница 20: ...10 Installation rules and restrictions...
Страница 54: ...44 Connecting an R100 chassis to an Ethernet network...
Страница 78: ...68 System messages at startup...
Страница 140: ...130 Replacing the CompactFlash unit subassembly...
Страница 164: ...154 Index...