Operating Instructions EBL512, V1.44.x
60
24
Disable or re-enable (H2)
A whole zone, one or more alarm points within a zone and/or control
outputs can be disabled via menus H2/B1-B3. This possibility can be
used when a temporary disablement is wanted (e.g. when the premises
are being restored, etc.).
Pre-alarms and fire alarms from the disabled alarm points will be
disabled. Faults will
not
be disabled.
Addressable manual call points can
not
be disabled.
Up to 100 alarm points, zones and/or outputs can be disabled.
It is not possible to exceed the limit. A warning message will be
shown:
Don't forget to re-enable
via menus H2/B4-B6 or use automatic re-
enablement for zones and alarm points.
Disablements are indicated by LED "Disabled" (L10).
Disablements (and faults) are indicated by a 2-sec. beep when an open
control unit door is being closed.
NOTE!
Don't re-enable a zone and then disable the same zone immediately.
Re-enabling takes about 2 seconds (normally) and up to 15 seconds.
(All alarm points have to, among other things, be "reset" before they
can be re-enabled).
Max. disconnected objects reached!
Disconnection not performed.
ACCEPT?