Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
84
27.4
Direction for communication on COM-loop
(H5/A3)
To make trouble shooting easier (e.g. during the commissioning) it is
possible to lock the communication on a COM or BS4 loop in one
direction.
(The communication direction is automatically changed two times per
24 hours, to ensure that the wires are okay.).
NOTE!
The locking only works as long as you "see the text in the
menu A3", i.e. when you log out or if you are automatically logged
out, the communication direction will be "reset" to the normal
direction for that time.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for
programming (H5)", see
page 81.
Scroll to menu A3
Direction for communication on
COM-/BS4-loop ACCEPT? A3
"A"
Select type of loop: 0 (0=COM, 1=BS4)
ACCEPT?
Push "A" or "1" and "A" to
accept. ON is indicated by
LED "Fault". This mode
is ON until turned OFF in
this menu (A2).
Lock COM-loop: 0 (0-3)
Unit: 00 (0-29) ACCEPT?
"A"
or
"1", "A"
Lock direction on BS4-loop: 0,
Board: 0, CU: 00 ACCEPT?
Write loop number (board
number) and control unit
number. Push "A" to
accept.
"A"
COM-loop is currently communicating in
A-direction ACCEPT?
(When you have selected a BS4 loop, the
text in this menu will still be COM loop).
(May be B-direction
instead.).
Push "A" to change
direction. Push "Return"
to finish (back to menu
A3).
"Return"
Direction for communication on
COM-/BS4-loop ACCEPT? A3
Scroll or push "Return" to
H5. Scroll or push
"Return" to logout.