Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
19
6.3
Access level 3
From access level 2
17
, the user can login to access level 3, which gives
access to the following menus, normally used by service personnel:
Same menus as in access level 2 plus the following:
H8 Maintenance
S1 Disable or re-enable outputs for routing equipment (Fire
brigade tx & Fault tx)
S2 Disconnect COM loop.
S3 Re-connect Loop.
S4 Acknowledge service signal.
S5 Safe shut down of control unit.
S6 Activate address in alarm mode.
S7 Synchronize the control units.
S8 Change access code for maintenance (access level 3).
17
If code for access level 3 or 4 has been used to login to access level 2, new
login to access level 3 is not required.
Содержание EBL512
Страница 2: ...This page has deliberately been left blank...
Страница 114: ...This page has deliberately been left blank...
Страница 115: ...This page has deliberately been left blank...
Страница 116: ...Citadellsv gen 23 SE 211 18 Malm Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 Home page www mfstech com...