Iris

Conventional fire detectors

ID100 - optical smoke detector

ID200 - temperature detector
ID300 - multicriteria detector

ATTENTION!

For  information  regarding  device  placement,  coverage  and  method  of  installation,  refer  to
the established standard regulations and codes relating to automatic fire-detection systems.
Iris series detectors are compliant with EN54-7: Smoke detectors – Point detectors using the
scattered  light  principle,  light  transmission  or  ionization  (ID100  and  ID300  models  only)
and EN54-5: Heat detectors – point detectors (for ID200 and ID300 models only).

Product description

Iris series detectors offer wide-spectrum detection of smoke particles generated by the majority of fires. They
are suitable for most applications and provide first-rate early warning.
The EITK-DRV driver, supplied by INIM Electronics, allows you to change the operating parameters to suit specific
environment  conditions.  This  device  permits  easy  programming  and  verification  of  contamination  and
performance. For further details, refer to “Using the EITK-DRV driver” section.
During standby status, these detectors have low current draw, 80



A. However, in the event of alarm the current

draw increases to a maximum of 40mA thus signalling the condition to the control panel. 
INIM  Electronics  offers  three  Iris  series  conventional  fire-detectors,  which  can  be  identified  by  the  technical
specifications/serial number on the back of the detector.

ID100

Optical  detector  equipped with  a reference  chamber  based  on  the scattered light
principle (Tyndall effect). This detector must be  installed  in  draught and  obstacle
free place which guarantees appropriate air-flow into the reference chamber.
The  detector  will  trigger  an  alarm  when  the  level  of  smoke  inside  the  reference
chamber reaches the following values:
• 0.08 dB/m (mode set via the EITK-DRV)
• 0.10 dB/m (mode set via the EITK-DRV)
• 0.12 dB/m (pre-set mode)
• 0.15 dB/m (mode set via the EITK-DRV)

ID200

Heat  detector  with  heat-sensitive  element  capable  of  sensing  the  temperature
within the protected environment.
The operating modes, programmable via the EITK-DRV are:
• “A1R” (pre-set); the detector signals alarm status when the temperature within the protected

environment exceeds 58 °C or when the temperature undergoes anomalous changes.

• “B”;  the  detector  signals  alarm  status  when  the  temperature  within  the  protected

environment exceeds 72°C.

• “A2S”;  the  detector  signals  alarm  status  when  the  temperature  within  in  the  protected

environment exceeds 58°C.

• “BR”;  the  detector  signals  alarm  status  when  the  temperature  within  the  protected

environment exceeds 72° or when it senses a rapid temperature rise.

ATTENTION!

The operating modes of the “A2S” and “BR” are not certified.

ID300

Optical-heat detector with heat sensitive element and optical smoke chamber. The
combination  of  values  provides  (in  accordance  with  the  operating  mode  selected
via  the  EITK-DRV  driver) high  immunity  to nuisance  alarms  and  an  exceptionally
sensitive detector which is capable of swift response to fires characterized by low
smoke emission. 
The operating modes, programmable via the EITK-DRV driver are:
• “PLUS”  (pre-set);  the  detector  signals  alarm  status  when  smoke  in  the  protected

environment  exceeds  the  programmed  threshold  (programmed  as  described  for  the
ID100  model)  or  when  the  temperature  within  the  protected  environment  exceeds  the

EN54-7:2000+A1+A2

ID100 NNNNNNNN   ID100 NNNNNNNN

ID100

0832 

0832-CPR-F1152
MADE IN ITALY 

991c/01 

NNNNNNNN

*NNNNNNNN*

YYYY/MM 

FW: FF.WW 

CONVENTIONAL

OPTICAL SMOKE DETECTOR

EN54-5:2000+A1

ID200 NNNNNNNN   ID200 NNNNNNNN

ID200

0832 

0832-CPR-F1243

MADE IN ITALY 

991e/01 

NNNNNNNN

*NNNNNNNN*

YYYY/MM 

FW: FF.WW 

CONVENTIONAL

CLASS P HEAT DETECTOR

EN54-5:2000+A1

EN54-7:2000+A1+A2

ID300 NNNNNNNN   ID300 NNNNNNNN

ID300

0832 

0832-CPR-F1153
MADE IN ITALY 

991a/01 

NNNNNNNN

*NNNNNNNN*

YYYY/MM 

FW: FF.WW 

CONVENTIONAL

MULTI OPTICAL SMOKE AND CLASS P HEAT DETECTOR

0832

0832-CPR-F1152
0832-CPR-F1243
0832-CPR-F1153

991c/01

991e/01
991a/01