ATTENTION!
For information regarding device placement, coverage and method of installation, refer to
the established standard regulations and codes relating to automatic fire-detection systems.
Iris series detectors are compliant with EN54-7: Smoke detectors – Point detectors using the
scattered light principle, light transmission or ionization (ID100 and ID300 models only)
and EN54-5: Heat detectors – point detectors (for ID200 and ID300 models only).
Product description
Iris series detectors offer wide-spectrum detection of smoke particles generated by the majority of fires. They
are suitable for most applications and provide first-rate early warning.
The EITK-DRV driver, supplied by INIM Electronics, allows you to change the operating parameters to suit specific
environment conditions. This device permits easy programming and verification of contamination and
performance. For further details, refer to “Using the EITK-DRV driver” section.
During standby status, these detectors have low current draw, 80
A. However, in the event of alarm the current
draw increases to a maximum of 40mA thus signalling the condition to the control panel.
INIM Electronics offers three Iris series conventional fire-detectors, which can be identified by the technical
specifications/serial number on the back of the detector.
ID100
Optical detector equipped with a reference chamber based on the scattered light
principle (Tyndall effect). This detector must be installed in draught and obstacle
free place which guarantees appropriate air-flow into the reference chamber.
The detector will trigger an alarm when the level of smoke inside the reference
chamber reaches the following values:
• 0.08 dB/m (mode set via the EITK-DRV)
• 0.10 dB/m (mode set via the EITK-DRV)
• 0.12 dB/m (pre-set mode)
• 0.15 dB/m (mode set via the EITK-DRV)
ID200
Heat detector with heat-sensitive element capable of sensing the temperature
within the protected environment.
The operating modes, programmable via the EITK-DRV are:
• “A1R” (pre-set); the detector signals alarm status when the temperature within the protected
environment exceeds 58 °C or when the temperature undergoes anomalous changes.
• “B”; the detector signals alarm status when the temperature within the protected
environment exceeds 72°C.
• “A2S”; the detector signals alarm status when the temperature within in the protected
environment exceeds 58°C.
• “BR”; the detector signals alarm status when the temperature within the protected
environment exceeds 72° or when it senses a rapid temperature rise.
ATTENTION!
The operating modes of the “A2S” and “BR” are not certified.
ID300
Optical-heat detector with heat sensitive element and optical smoke chamber. The
combination of values provides (in accordance with the operating mode selected
via the EITK-DRV driver) high immunity to nuisance alarms and an exceptionally
sensitive detector which is capable of swift response to fires characterized by low
smoke emission.
The operating modes, programmable via the EITK-DRV driver are:
• “PLUS” (pre-set); the detector signals alarm status when smoke in the protected
environment exceeds the programmed threshold (programmed as described for the
ID100 model) or when the temperature within the protected environment exceeds the
EN54-7:2000+A1+A2
ID100 NNNNNNNN ID100 NNNNNNNN
ID100
0832
0832-CPR-F1152
MADE IN ITALY
991c/01
NNNNNNNN
*NNNNNNNN*
YYYY/MM
FW: FF.WW
CONVENTIONAL
OPTICAL SMOKE DETECTOR
EN54-5:2000+A1
ID200 NNNNNNNN ID200 NNNNNNNN
ID200
0832
0832-CPR-F1243
MADE IN ITALY
991e/01
NNNNNNNN
*NNNNNNNN*
YYYY/MM
FW: FF.WW
CONVENTIONAL
CLASS P HEAT DETECTOR
EN54-5:2000+A1
EN54-7:2000+A1+A2
ID300 NNNNNNNN ID300 NNNNNNNN
ID300
0832
0832-CPR-F1153
MADE IN ITALY
991a/01
NNNNNNNN
*NNNNNNNN*
YYYY/MM
FW: FF.WW
CONVENTIONAL
MULTI OPTICAL SMOKE AND CLASS P HEAT DETECTOR
0832
0832-CPR-F1152
0832-CPR-F1243
0832-CPR-F1153
991c/01
991e/01