Operating Instructions EBL512, V1.44.x
59
Perform the tests as quickly as possible, since the output for routing
equipment (fire brigade tx) is disabled (also the parts of the zones in
test mode, not visible for the test personnel, are disabled).
In the tested alarm point, the LED will light up, and the LEDs "Fire"
(L1) in the C.U. will light up, about ten seconds, then the alarm point
will be automatically reset. The printer, if available, will print out
every tested alarm point (Zone: xxx Address: xx Time: HH.MM).
Push "A" to stop the test mode.
Some regulations say that the fire alarm routing equipment (Fire alarm
tx) also should be tested. If the equipment don't have this test
possibility, it can only be done by generating a real fire alarm.
NOTE!
If the control unit door is left open, the output(s) for routing
equipment (fire brigade tx) may be disabled (if programmed so in
Win512).
A sensor in test mode will not be able to activate fault.
Action
Text in display
Comments
"A"
Monthly test is completed!
ACCEPT
The LED "Test mode" is
turned OFF.
"A"
Perform monthly test
ACCEPT? H1
Scroll or push "Return" to
logout.