15 Alarm
reset
15.1 Pre-alarm
reset
Pre-alarm is automatically reset (i.e. when the sensor value + offset
for pre-alarm, is below the pre-alarm level).
15.2
Fire alarm reset
•
The fire alarm, shown in the FBP display(s), on the first row
to the left, will be reset when the push button "Reset" (P3) is
pushed
NOTE! The push button has to be in reset position for a
minimum of 0.5 sec.
•
Output(s), programmed for this fire alarm, is(are) reset.
If more than one fire alarm is activated (i.e. LEDs "Alarms queued"
(L2) are lit) the next fire alarm in the queue is now shown in the
display, on the first row to the left. It has to be reset the same way as
the first one.
NOTE!
If the sounders have been silenced, LED "Silence" (L7) is lit. Push
"Silence" (P2) to return to normal state (LED "Silence" will be turned
OFF).
When all fire alarms are reset
, LEDs "Alarms queued" are turned
OFF and the display is empty
36
.
All outputs (for fire alarm) have been reset.
The key has to be put back into the key cabinet
within 5 minutes
. If
not, a fault will be generated and a fault message will be shown in the
FBP display(s) as follows:
Indications and activations are the same as for any other fault, see
chapter "Fault", page 35.
15.3
Heavy smoke alarm reset
If a heavy smoke alarm has been activated, it will be reset at the same
time as the corresponding fire alarm is reset and resp. output(s) will be
reset.
36
If there is a fault condition (e.g. caused by the fire), a fault message will
now be shown in the display.
FAULT: Key box, control unit: No.
Date: MM-DD Time: HH:MM