Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
63
24.3
Disable control output (H2/B3)
Every control output can be individually disabled.
Disabled outputs are listed in menu H4/U1. From this menu, it's also
possible to get a print-out.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 57.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B3.
Disable control output
ACCEPT? B3
"A"
Disable control unit: 00 Type: 0
0=RU/SU 1=S 2=R 3=RE 4=ES ACCEPT?
(4=ES not shown in Swedish (RUS)
convention)
Write C.U. No. and push:
"0"=RU4 (2265) or
SU4 (2262 / 2263),
"1"=S0-S3,
"2"=R0-R1 or
"3"=Relay board 1581.
"4"=1583 board output
"Extinguishing system".
Push "A" to accept.
"A"
Depending on the
chosen type, 0, 1, 2, 3
resp. 4, the following
will be shown:
Disable 00 0000 control output 0
ACCEPT?
Disable S0
ACCEPT?
Disable R0
ACCEPT?
Disable relay board 0 output 0
ACCEPT?
Disable output for extinguishing system
on 1583 board, CU 00 ACCEPT?
Write the data. Push "A"
to accept.
"A"
Disable control unit: 00 Type: 0
0=RU/SU 1=S 2=R 3=RE 4=ES ACCEPT?
If more disablements
shall be done, continue
like above. If not, push
"Return" to menu B3.
Scroll or push "Return"
to menu H2. Scroll or
push "Return" to logout.