Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
56
NOTE!
By reset/restart, the Fault tx output(s) will be "activated".
The "restart" will last for up to 2 minutes. During this 2 min. period
no fire alarm can be activated.
A
fault
is generated in the system and the following message will be
shown in the display:
Regarding code xx and yy - y, see page 43. This fault is also indicated
by LEDs "Fault tx" (L19) and "Fault" (L8). (Also LED "
Fault
System" (L12) can be lit).
After fault acknowledge (menu H6), the LEDs will be turned OFF if
there are no other faults.
NOTE!
After reset, required disablements have to be done.
FAULT: Restart CU nn code xx yyyyyyyyyy
Date: MM-DD Time: HH:MM