Operating Instructions EBL512, V1.44.x
65
24.5
Re-enable zone / address (H2/B5)
Disabled alarm points, zone / addresses, are listed in menu H4/U1.
From this menu, it's also possible to get a print-out.
Re-enabling via this menu, has higher priority than automatic re-
enabling.
When all alarm points have been re-enabled, The LED "Disabled" will
be turned OFF, if there are no other disablements in the system.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 57.
Scroll to menu H2:
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B5.
Re-enable zone / address
ACCEPT? B5
"A"
Re-enable zone: 000 Address: 00
ACCEPT? L
If there are no zone /
addresses to re-enable,
menu B4 will be shown
again.
If it's the correct zone /
address to re-enable, push
"A" to accept. If not, scroll
or write the wanted zone /
address and push "A" to
accept.
"A"
Re-enable zone / address
ACCEPT? B5
If more re-enablements
shall be done, continue like
above. If not, scroll or
push "Return" to menu H2.
Scroll or push "Return" to
logout.