Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
74
26.4
Activated 2-zone/address dependent
(H4/U4)
2-zone dependency
(Win512, dialog box "System"): When only one
zone
is in alarm status, the LEDs "Fire" (L1) are flashing but there is
no fire alarm presentation in the FBP display(s) or display units.
51
2-unit dependent
(Win512, COM loop unit dialog box): When only
one
zone / address
(alarm point / unit) is in alarm status, the LEDs
"Fire" are flashing but there is no fire alarm presentation in the FBP
display(s).
52
In menu H4/U4, this
2-zone
or
2-unit dependent
(zone / address) in
alarm status is shown. From this menu, it's also possible to get a print-
out.
51
When two or more
zones
, dependent on each other, are in alarm status,
fire alarm will be activated in the system.
52
When two or more
units
(zone / addresses), dependent on each other, are
in alarm status, fire alarm will be activated in the system.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 57.
Scroll to menu H4.
Present system status on display and
printer ACCEPT? H4
"A"
Disablement
Printout: (1=yes) U1
Scroll to menu U4.
Activated 2-zone/address dependent
zone/address Printout: (1=yes) U4
Push "1" for an
automatic print-out.
Push "A" for
presentation in the
display.
"1"
or
"A"
When "A" is pushed, zone & address will be shown in the
display, e.g:
ALARM zone XXX address XX
(co-incidence)
This is a list in which
you can scroll. If there
are no "alarms", if
"Return" is pushed and
after the last print-out,
menu U4 will be shown
again.
"Return"
Activated 2-zone/address dependent
zone/address Printout: (1=yes) U4
Scroll or push "Return"
to menu H4. Scroll or
push "Return" to logout.