Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
97
30.3
Disconnect COM-loop (H8/S2)
Before physical connection / disconnection of loop units, etc. to a loop
or zone line, the "loop" should be disconnected (disabled), i.e. no
voltage on the "loop" to avoid damage on the units and control unit.
Don’t forget to re-connect the loop / zone line again, via menu H8/S3.
BS4 loop require an Autronica interface board 1584 in the control
unit. DET8 "loop" require an 8 zones expansion board 1580 in the
control unit.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for
maintenance", see page 95.
Scroll to menu S2.
Disconnect COM-Loop
ACCEPT? S2
"A"
Disconnect type: 0 (0=COM, 1=BS4,
2=DET8, 3=loop Unit) ACCEPT?
Push:
"0"=COM loop
"1"=BS4 loop
"2"=Expansion board 1580
"3"=Addr. zone interface
2226 / 2335. Push "A" to
accept.
Disconnect COM-Loop: 0, CU: 00
ACCEPT?
Disconnect BS4-Loop: 0, Board: 0,
CU: 00 ACCEPT?
Disconnect DET8-input: 0, Board: 0,
CU: 00 ACCEPT?
"A"
Depending on the
chosen type, 0, 1, 2 or
3, the following will be
shown:
Disconnect input technical no.: 000000
ACCEPT?
Write the required
numbers. Push "A" to
accept.
"A"
Disconnect type: 0 (0=COM, 1=BS4,
2=DET8, 3=loop Unit) ACCEPT?
LED "Disabled" indicates
disconnected loops, etc..
Continue to disconnect or
push "Return" to menu S2.
"Return"
Disconnect COM-Loop
ACCEPT? S2
Scroll or push "Return" to
return to menu H8. Scroll
or push "Return" to logout.
Содержание EBL512
Страница 2: ...This page has deliberately been left blank...
Страница 114: ...This page has deliberately been left blank...
Страница 115: ...This page has deliberately been left blank...
Страница 116: ...Citadellsv gen 23 SE 211 18 Malm Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 Home page www mfstech com...