FAULT: Restart CU nn code xx yyyyyyyyyy
Control unit restart (reset) has occurred.
nn:
Control unit number (00-29)
xx=00:
Power On Reset. (Power supply connected)
xx=01: Watchdog
Reset.
xx=02:
Accidental jump to reset vector.
xx=03:
External reset caused by external watchdog/user
(e.g. after SSD download) or RESET jumper JP4
on the main board 1556, has been used.
xx=4-16: Unexpected
interrupt.
If xx=01,02 or 04-16 appear often, call for service personnel/
engineer.
yy – y =
memory address (before restart)
FAULT: ROM memory control unit xx
A fault in control unit xx SW. This is very serious. Call for service
personnel/engineer immediately.
FAULT: RS232-comm in gateway, CU xx
Gateway GW512 is/are installed in the system. No/not correct
communication on the RS232 line between GW512 and the
EBL1000/2000 Main Control Unit number. xx=sub control unit
number for the GW512.
FAULT: Sensor techn. no. xxxxxx
•
The sensor is removed from its sensor base.
•
Faulty sensor.
FAULT:Sh-circ loop x, CU xx, CU <->ASF0
FAULT:Sh-circ loop x, CU xx,ASF0<->ASF1
FAULT:Sh-circ loop x, CU xx,ASF1<->ASF2
FAULT:Sh-circ loop x, CU xx,ASF2<->ASF3
FAULT:Sh-circ. loop x, CU xx, ASF3<->CU
FAULT:Sh-circ. loop x, CU xx, ASF2<->CU
FAULT:Sh-circ. loop x, CU xx, ASF1<->CU
FAULT:Sh-circ. loop x, CU xx, ASF0<->CU
Short circuit on the COM loop "x" (
one, two, three or four short