Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
14
5
LED indicators and push buttons
LEDs and push buttons vary according to type and configuration
(convention / country / language).
LED indicators on the Fire Brigade Panel (FBP)
LED indicator
Indicating
L1
Fire (5 red)
Fire alarm generated.
L2
Alarms queued (2 red) More than one alarm point/zone have generated fire alarm.
L3
Extinguishing (red)
Output(s) for extinguishing equipment activated.
L4
Ventilation (yellow)
Output(s) for fire/smoke ventilation equipment activated.
L5
Fire brigade tx (red)
Output(s) for fire brigade tx (routing equipment) activated
L6 (Zone/Detector
not
reset)
5
(An alarm point has been reset while still in alarm status, i.e.
it is non-reset ("isolated") and has to be re-enabled.)
L7
Silence (yellow)
The sounders (alarm devices) are silenced by the push button
"Silence".
L3-L5 can be individually programmed to indicate when it's normal
trigger condition is met or when a programmable input is activated
(e.g. L5 will be turned on when an input is activated by a TX output.
Push buttons on the Fire Brigade Panel (FBP)
Push button
Operation/function
P1
Scroll (red)
Used, when LEDs "Alarms queued" are lit, to scroll/browse
through the queued alarms.
P2 Silence
(yellow)
6
Used to silence the sounders (i.e. to "reset" resp. outputs).
LED "Silence" indicates silenced sounders.
P3
Reset (red)
Resets the fire alarm displayed in the LCD. When more than
one fire alarm is generated (LEDs "Alarms queued" are lit).
Each fire alarm has to be individually reset.
P4
Lamp test (green)
7
To test all the LEDs on the FBP and the CP.
P5 Evacuate
(green)
8
Manual activation of sounders (alt. Paper feed).
5
Normally only used in Swedish configuration / convention.
6
Has a special function in some configurations / conventions.
7
Not used in all configurations / conventions. If not used, it's black and has
no function.
8
Normally only used in Brittish Standard convention. In B.S. (Marine
application) convention it has the function "Paper feed". Otherwise it's black
and has no function (or the function "Paper feed").