13.2 Fire
alarm
A sensor generates fire alarm for an offset (level) that can normally
not
be changed
26
.
In case of a fire alarm, the following will happen:
•
The buzzer in the control unit sounds 0.8 sec. each 0.8
th
sec.
(0.8/0.8sec.).
•
Output(s) for routing equipment (Fire brigade tx) is (are)
activated.
•
Output(s) for sounders (type 3 = alarm devices) is(are)
activated.
•
Output(s)
27
for fire alarm is(are) activated.
•
LEDs "Fire" (L1) are blinking.
•
On the first row in the FBP display(s), the presentation
number is shown (for the first fire alarm). On the second
row, is a user definable text message shown (if
programmed).
Example; fire alarm zone 123 address 45:
•
If more than one fire alarm are generated
28
, the LEDs
"Alarms queued" (L2) are blinking. To scroll through the
alarms, use push button "Scroll" (P1).
Example; more than one fire alarm:
•
The alarms are stored in a circular buffer and when scrolling
from the last to the first alarm, the LEDs "Alarms queued"
will be turned off for three seconds.
•
Each fire alarm is printed
29
; zone-address,
u
ser definable
text message
(if programmed) and time.
Each fire alarm has to be individually reset, see chapter "Alarm reset",
page 33.
26
Via Win512 it is possible to change the fire alarm offset (level). A special
access code is required.
27
And output(s) programmed for this specific fire alarm.
28
Only the ten latest fire alarms will be displayed in the ext. FBPs.
29
When printer is available (e.g. control unit 1549).
Alarm No.001:123-45
User definable text message. . . . . . .
Alarm No.001:123-45 Last No.011:555
User definable text message (for 123-45)