Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
62
24.2
Disable zone / address (H2/B2)
Every addressable alarm point connected to the COM loop can be
individually disabled.
Disabled alarm points, zone / addresses, are listed in menu H4/U1.
From this menu, it's also possible to get a print-out.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 57.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B2.
Disable zone / address
ACCEPT? B2
"A"
Disable zone: 000 Address: 00
ACCEPT?
Write zone number and
address
(e.g. 001 / 01)
Disable zone: 001 Address: 01
ACCEPT?
Push "A" to accept.
"A"
Automatic re-enabling:0 (0=No,1=Yes)
Time: HH:MM ACCEPT?
(Default is current time + 3 hours)
Push "1" for aut. re-
enabling and accept or
change the time (max. 24
hours). Push "A" to
accept. LED "Disabled"
will light up.
"A"
Disable zone: 000 Address: 00
ACCEPT?
If more disablements
shall be done, continue
like above. If not, push
"Return" to menu B2.
Scroll or push "Return" to
menu H2. Scroll or push
"Return" to logout.