Ds230_03a_oi_e.doc / Jun-15
Page 27 / 100
5.11.
DIL switch
The 3-position DIL switch [S1] is located at the front of the unit
(only accessible, if no display-unit is connected).
3-pos DIL switch [S1]
The following unit-states can be set by the DIL switch:
Slider
Condition Unit-State
1
ON
„Normal Operation“ - Parameter access disabled
OFF
„Factory Settings“ - with next power-on, all Parameters will be reset to default values
2
ON
„Normal Operation“ - Parameter access disabled
OFF
„Self Test Message“ - with next power-on, the unit will transmit a self test protocol
via USB interface
(without “Self Test Message” booting of the start up is faster)
3
ON
„Normal Operation“ - Parameter access disabled
OFF
„Programming Mode“ – allows access to the Parameters (by display unit or PC)
„Programming Mode“ (DIL switch) only for start-up
Set all DIL switch sliders to „ON“ after start-up
Protect the DIL switch sliders after start-up (e. g. by covering with an adhesive tape)
Normal operation is only permitted when the yellow LED is permanently off
The safety function of the unit cannot be guaranteed before the commissioning
is completed.
5.11.1.
Boot time
DIL Nr. 2
Boot time
ON = Normal Operation
After connecting the supply voltage, the device is ready for operation
after about 2 s
OFF = Self Test Message
After connecting the supply voltage, the device is ready for operation
after about 8 s
Содержание DS230 Series
Страница 10: ...Ds230_03a_oi_e doc Jun 15 Page 10 100 4 3 DS236 Block Diagram 4 4 DS236 Connections...
Страница 11: ...Ds230_03a_oi_e doc Jun 15 Page 11 100 4 5 DS240 Block Diagram 4 6 DS240 Connections...
Страница 12: ...Ds230_03a_oi_e doc Jun 15 Page 12 100 4 7 DS246 Block Diagram 4 8 DS246 Connections...
Страница 99: ...Ds230_03a_oi_e doc Jun 15 Page 99 100 11 1 Dimensions inclusive BG230 at front Front Rear DS230 BG230 option...
Страница 100: ...Ds230_03a_oi_e doc Jun 15 Page 100 100 12 Certificate...