Ds230_03a_oi_e.doc / Jun-15
Page 69 / 100
Continuation “Switching Menu”:
No.
Parameter
Range
Default
058
Action Output
(output selection for overwriting)
:
The function to set fixed output conditions by overwriting is only
effective in the “Programming Mode” (see chapter
). It is used for
test purposes and allows to force each output to a defined switching
condition.
The „Action Output“ parameter selects the outputs to be tested.
The next Parameter „Action Polarity“ (parameter 059) is used to assign
the desired switching conditions to the selected outputs.
The outputs are selectable by using a 5 bit binary code:
Output:
RELAY
OUT4
OUT3
OUT2
OUT1
Bit
5
4
3
2
1
Binary:
10000
01000
00100
00010
00001
Value:
16
8
4
2
1
Example:
A setting of 14 (binary 01110) means that the outputs OUT2, OUT3 and
OUT4 are selected for overwriting.
REL
0
No overwriting
OUT4
1
Status see Action Polarity (parameter 059)
OUT3
1
Status see Action Polarity (parameter 059)
OUT2
1
Status see Action Polarity (parameter 059)
OUT1
0
No overwriting
After the test, this parameter must be reset to the "Default".
0 - 31
0
The safety function of the unit cannot be guaranteed before the commissioning is completed.
Содержание DS230 Series
Страница 10: ...Ds230_03a_oi_e doc Jun 15 Page 10 100 4 3 DS236 Block Diagram 4 4 DS236 Connections...
Страница 11: ...Ds230_03a_oi_e doc Jun 15 Page 11 100 4 5 DS240 Block Diagram 4 6 DS240 Connections...
Страница 12: ...Ds230_03a_oi_e doc Jun 15 Page 12 100 4 7 DS246 Block Diagram 4 8 DS246 Connections...
Страница 99: ...Ds230_03a_oi_e doc Jun 15 Page 99 100 11 1 Dimensions inclusive BG230 at front Front Rear DS230 BG230 option...
Страница 100: ...Ds230_03a_oi_e doc Jun 15 Page 100 100 12 Certificate...