Ds230_03a_oi_e.doc / Jun-15
Page 70 / 100
Continuation “Switching Menu”:
No.
Parameter
Range
Default
059
Action Polarity
(setting the output conditions)
:
This setting-function is only effective in the “Programming Mode” (see
chapter
) and requires a selection of the corresponding outputs
(see parameter 058).
For security reasons the 4 digital outputs are complementary, which
means that each output has one direct track and an inversed one
(marked by a slash „/“). During normal operation both tracks generally
must have opposite conditions, but in the test-mode arbitrary output-
conditions can be simulated.
The output-conditions are assignable by a 9 bit binary code:
0 - 511
0
OUT:
REL
4
/4
3
/3
2
/2
1
/1
Bit
9
8
7
6
5
4
3
2
1
Value:
256 128 64
32
16
8
4
2
1
Example:
A setting of 275 (binary 1 0001 0011) causes the following output
conditions (from left to right):
REL
1
Contact closed
OUT4
0
Low
/OUT4
0
Low
OUT3
0
Low
/OUT3
1
High
OUT2
0
Low
/OUT2
0
Low
OUT1
1
High
/OUT1
1
High
After the test, this parameter must be reset to the "Default".
060
Reserved
061
Reserved
The safety function of the unit cannot be guaranteed before the commissioning is completed.
Содержание DS230 Series
Страница 10: ...Ds230_03a_oi_e doc Jun 15 Page 10 100 4 3 DS236 Block Diagram 4 4 DS236 Connections...
Страница 11: ...Ds230_03a_oi_e doc Jun 15 Page 11 100 4 5 DS240 Block Diagram 4 6 DS240 Connections...
Страница 12: ...Ds230_03a_oi_e doc Jun 15 Page 12 100 4 7 DS246 Block Diagram 4 8 DS246 Connections...
Страница 99: ...Ds230_03a_oi_e doc Jun 15 Page 99 100 11 1 Dimensions inclusive BG230 at front Front Rear DS230 BG230 option...
Страница 100: ...Ds230_03a_oi_e doc Jun 15 Page 100 100 12 Certificate...