Ds230_03a_oi_e.doc / Jun-15
Page 57 / 100
Continuation „Main Menu“:
No.
Parameter
Range
Default
009
Error Simulation:
This Parameter is only allowed in the “Programming Mode”
(see chapter
) and serves only for test purposes during the
commissioning procedure. It allows to simulate and prevent the
following error messages:
0
Error state:
Sets the unit into error status. By using this Parameter
it is possible to check, if the entire follow-up system
reacts correctly at error status.
1
Normal state:
Before exiting the “Programming Mode”,
the Parameter always must be set to 1.
2
Error clearing:
All errors reported by the unit will be reset.
A direct changeover between 0 and 2 should be avoided
After the test, this parameter must be reset to the "Default".
0 - 2
1
010
Power-up Delay:
A delay time setting is recommended to ensure for all connected
encoders a safely power up and enough time for stabilization after
switching the encoder supply. The signal evaluation will start only
after the selected delay.
1 - 1,000
(sec.)
0,100
011
Reserved
012
Reserved
The safety function of the unit cannot be guaranteed before the commissioning is completed.
Содержание DS230 Series
Страница 10: ...Ds230_03a_oi_e doc Jun 15 Page 10 100 4 3 DS236 Block Diagram 4 4 DS236 Connections...
Страница 11: ...Ds230_03a_oi_e doc Jun 15 Page 11 100 4 5 DS240 Block Diagram 4 6 DS240 Connections...
Страница 12: ...Ds230_03a_oi_e doc Jun 15 Page 12 100 4 7 DS246 Block Diagram 4 8 DS246 Connections...
Страница 99: ...Ds230_03a_oi_e doc Jun 15 Page 99 100 11 1 Dimensions inclusive BG230 at front Front Rear DS230 BG230 option...
Страница 100: ...Ds230_03a_oi_e doc Jun 15 Page 100 100 12 Certificate...