background image

PMP320HDW2v1 

3-31 

Preliminary 

JUL 2010 

   

   

1

 

Install the CMM4 power supply in a hut, wiring closet, or weatherized 
NEMAapproved enclosure.   It is designed for extreme temperatures but it is 
imperative to keep moisture away from the power converter.

 

2

 

Do not install the power supply within the CMM4 enclosure as it will increase 
the heat within the enclosure to an unacceptable level.   The CMM4 enclosure
is large to provide surface area for heat dissipation without the use of forced 
convection fans, not to provide space for additional high-power electronics.

 

3

 

For the DC side of a 56 VDC power supply, engineer the DC cable, selecting 
the wire gage from 

Table 4-1

.    Use either UV-resistant cable or shield the 

cable (as in a conduit) from UV rays.

 

4

 

 

Installing the power supply for the CMM4 

Chapter 3:  CMM4 Hardware Installation 

 

 

 

 

Installing the power supply for the CMM4

 

 

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

                         

 

 

 

 

 

 

 

 

WARNING

 

 

Although the output of the power supply is 29 VDC or 56 VDC, the power rating 

classifies the converter as a Class 2 electric device.   For this reason, whenever you 

work on power in the CMM4, you must first disconnect the DC supply from the AC 

power source. 

 

 

Select the appropriate procedure to install the power supply for the CMM4.    Directions are 
provided for a 56 VDC power supply and a procedure on how to install the 30 VDC power supply. 

 

If using both 30 VDC and 56 VDC, a 1000 Ohm 5W resistor must be installed across the 30 VDC 
+V and GND at the terminal block. 

 

 

56 VDC Power Supply Installation

 

 

 

Use the following procedure to install a 56 VDC power supply for the CMM4. 

 

 

Procedure 3-2     Installing a 56 VDC Power Supply for the CMM4 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connect the DC cable on the top of the connector.    Insert the +V lead into 
the  terminal  7  cage  clamp  and  insert  the  GND  (ground/return)  lead  into  the 
terminal 4 cage clamp.   To insert a lead into a cage clamp, insert a thin-blade 
screwdriver in the secondary cage clamp hole and lever the screwdriver away 
from the main cage clamp hole. 

 

Continued

 

Содержание PMP 320

Страница 1: ...PMP 320 Hardware Installation PMP320HDW2v1 JUL 2010 Preliminary 2010 Motorola Inc All Rights Reserved ...

Страница 2: ...e deemed to grant either directly or by implication estoppel or otherwise any license under the copyrights patents or patent applications of Motorola or other 3rd Party supplied software except for the normal non exclusive royalty free license to use that arises by operation of law in the sale of a product Restrictions Software and documentation are copyrighted materials Making unauthorized copies...

Страница 3: ...em to the PMP 320 Support Team 5 U S and Canada 5 Latin America and Central America 5 Europe Middle East and Africa 5 Asia Pacific 6 Chapter 1 Product Description Access Point AP 1 3 Site preparation 1 5 Cluster Management Module 4 CMM4 1 6 What is included when the CMM4 unit is shipped 1 8 Point to Multi point Cluster Subscriber Module 320 1 9 Site considerations 1 10 Point to Multi point Connect...

Страница 4: ... connecting the antenna 2 5 Earth Ground cable assembly and connection 2 11 LED indicator 2 14 Attach the AP assembly to a pole 2 15 Surge Suppression Information 2 19 AP Hardware Installation complete 2 19 Chapter 3 CMM4 Hardware Installation Before you begin 3 3 AvoidingHazards 3 3 Grounding Equipment 3 3 Grounding Infrastructure Equipment 3 4 PMP320HDW2v1 i ...

Страница 5: ...Antenna 3 7 GPS Coax Cable 3 8 Installing the power supply for the CMM4 3 10 56 VDC Power Supply Installation 3 10 30 VDC Power Supply Installation 3 12 Surge Suppressors 3 13 600SSD and 200SSB Surge Suppressor installation 3 13 L COM Surge Suppressor installation 3 14 Installing the CMM4 3 17 Cabling a CMM4 3 20 LED indicators 3 23 Power Faults 3 24 Configuring CMM4 ports 3 25 Other Installation ...

Страница 6: ...the bracket assembly to a pole 5 9 Aligning the CSM for best signal strength 5 10 Connecting the CSM to the Ethernet cable Earth Ground the Surge Suppressor 5 12 Ethernet Cable Assembly 5 12 Running cables through the wall of the building 5 14 Installing the 600SSD Surge Suppressor 5 15 Connecting the ground wire 5 16 Connecting the power supply and the Ethernet cable to the computer 5 17 Chapter ...

Страница 7: ... 18 Chapter 7 Connectorized CSM Antenna Installation Instructions Antenna Types used with the Connectorized CSM 7 2 Dual Polarization Dual Slant Subscriber Antenna 7 2 Omni Directional Base Station Antenna 7 6 Chapter 8 Regulatory Legal and Safety Notices IMPORTANT NOTE ON MODIFICATIONS 8 2 NATIONAL AND REGIONAL REGULATORY NOTICES 8 3 U S Federal Communication Commission FCC Notification 8 3 Indus...

Страница 8: ...Preliminary JUL 2010 iv PMP320HDW2v1 ...

Страница 9: ...ting the AP to the tower 2 15 Figure 3 1 AP Installation and wiring 3 2 Figure 3 2 600SSD surge suppressor connectors 3 13 Figure 3 3 L COM surge suppressor 3 15 Figure 3 4 CMM4 unit opened showing connection details 3 18 Figure 3 5 CMM4 connection diagram located on the door of the unit 3 20 Figure 3 6 Port Status Showing Power Fault 3 25 Figure 4 1 RJ 45 Straight through connections 4 4 Figure 4...

Страница 10: ... surge suppressor to the CSM power injector and the CSM 6 17 Figure 6 8 CSM 320 power injector 6 17 Figure 7 1 Dual Polarization Dual Slant Subscriber Antenna 7 2 Figure 7 2 Mounting Bracket Parts Identification 7 5 Figure 7 3 Dual Polarized Dual Slant Subscriber Antenna Rear View for Mounting Assembly 7 5 Figure 7 4 Omni Directional Base Station Antenna Identification 7 7 Figure 7 5 Omni Directio...

Страница 11: ...Electrical Specifications 7 3 Table 7 2 Dual Polarized Dual Slant Subscriber Antenna Mechanical Specifications 7 3 Table 7 3 Dual Polarized Dual Slant Subscriber Antenna Environmental Specifications 7 3 Table 7 4 Dual Polarized Dual Slant Subscriber Antenna Parts List 7 4 Table 7 5 Omni Directional Base Station Antenna Electrical Specification 7 7 Table 7 6 Omni Directional Base Station Antenna Me...

Страница 12: ...nd equipment installers This installation manual covers the physical installation procedures of the hardware for the PMP 320 product line which encompass the Cluster Access Point CAP or AP Cluster Manager Module 4 CMM4 and the Cluster Subscriber Module CSM Software installation and configuration information for the AP and the CSM are covered in the PMP 320 Administration and Configuration PMP320HD...

Страница 13: ...tory The following sections show the revision status of this document Version information The following table describes the changes made to this document Version Date of issue Description 1 JUL 2010 Preliminary version for FCC UL review 2 PMP320HDW2v1 ...

Страница 14: ...E If this document was obtained when attending a Motorola training course it is not updated or amended by Motorola It is intended for TRAINING PURPOSES ONLY If it was supplied under normal operational circumstances to support a major software release then Motorola automatically supplies corrections and posts on the Motorola customer website Cross references References made to external publications...

Страница 15: ...ilities and environmental variables that appear on the screen are shown like this sentence Items of interest within a screen display appear like this sentence Special key sequences Special key sequences are represented as follows CTRL c or CTRL C Press the Ctrl and C keys at the same time CTRL SHIFT c or CTRL SHIFT C Press the Ctrl Shift and C keys at the same time ALT f or ALT F Press the Alt and...

Страница 16: ...ses and features enabled on the system Escalate the problem to the PMP 320 Support Team Escalate any issues to the Wireless Broadband Support Team by contacting the support team in your area U S and Canada E mail EMS EICC RM motorola com Telephone 1 866 961 9288 Latin America and Central America E mail EMS EICC RM motorola com Telephone Argentina 0800 666 2789 Brazil 0800 891 4360 Columbia 01 800 ...

Страница 17: ...erlands 0202061404 Norway 24159815 Portugal 0217616160 Spain 0912754787 Russia 810 800 228 41044 Saudi Arabia 800 844 5345 South Africa 0800981900 United Kingdom 0203 0277499 Asia Pacific E mail WiBBsupport apac motorola com Telephone 6048503854 9 AM through 5 PM Malaysia time 420 533 336 946 outside the 9 am through 5 PM hours 6 PMP320HDW2v1 ...

Страница 18: ... providers with broadband network service for any size operation Wireline service providers with broadband wireless extensions for existing DSL or cable networks As shown in Figure 1 1 a Raintight PMP 320 network consists of APs Cluster Access Point CAP 320 Access Points usually tower mounted in a four sector configuration CPE Cluster Subscriber Module CSM 320 Customer Premise Equipment CPE or als...

Страница 19: ... Element Management System such as the Motorola One Point Wireless Manager DHCP Server Dynamic Host Configuration Protocol server DNS Server Domain Name System server CNUT Network Update Tool for updating device software Router optional Motorola offers PMP 320 equipment that operates in the spectrum ranges as shown in Table 1 1 Spectrum Range Operation Licensed Spectrum Ranges System Name AP Name ...

Страница 20: ...ration The AP is manageable by local web interface as well as SNMP or the Motorola One Point Wireless Manager WARNING Installing an AP involves height electricity and exposure to RF radio frequency energy To avoid personal injury follow applicable national and local safety regulations along with industry best practices Also follow the specific guidelines in this document including maintaining a su...

Страница 21: ...P The AP can be configured to either receive its IP address from a network DHCP server or be manually assigned its IP address can be configured to respond to SM DHCP requests either by relaying the requests to a network DHCP server or function as a DHCP server itself can be configured either to use an external AAA Authentication Authorization and Accounting server or use a minimal internal AAA ser...

Страница 22: ...d frequency information refer to the PMP 320 Administration and Configuration Guide located at http motorola wirelessbroadbandsup port com support library Site preparation Review the following site requirements before selecting the site for the installation of the PMP 320 CAP Verify that a good Earth Ground can be achieved at the site Verify that the power to the site is reliable and can be backed...

Страница 23: ...Sync over Power over Ethernet and integrated surge suppression on the controller board for up to 8 APs or BHs Both a custom 30 VDC power scheme and a custom 56 VDC power scheme are available Neither is the same as the later IEEE Standard 802 3af and neither is compatible with it Managed switching using a hardened EtherWAN switch The CMM4 ships with a 14 port EtherWAN switch and is also available w...

Страница 24: ... switch and how the port is managed or for information on earlier versions of the CMM4 units refer to the Cluster Management Module 4 User Guide located at http motorola wirelessbroadbandsupport com The controller board injects power and synchronization on up to eight Ethernet ports and provides the equivalent of 600SSD surge suppression on each of the eight ports The controller board is managed u...

Страница 25: ...ard and the EtherWAN Ethernet Switch U bolts and V brackets for pole mounting the CMM4 GPS Antenna GPS antenna pole mount kit A 1 hole cable gland insert for use on the DC power cable The CMM4 as shipped does not include Any power supply The appropriate power supply s 30 VDC and or 56 VDC must be ordered separately Ethernet cables to connect the CMM4 to APs backhauls or terrestrial feeds Coax cabl...

Страница 26: ...remise Equipment CPE or the Subscriber Module SM is the device that extends the broadband network or internet services to the end user through communication with the PMP 320 AP The key features of the CSM are an integrated 14 5 dBi gain antenna 802 3af power over Ethernet 4 VDC 802 16e standard fixed outdoor solution products that are available in the 3 3 GHz 3 8 GHz spectrum The CSM is managed by...

Страница 27: ...sible for the loss damage to the CSM while in their care Route and hide the ENET cables against the house following local installation codes This extra effort lowers the chance of a new home owner taking down the CSM and its wiring Avoid penetrating the roof this will help mitigate issues with leaks Work with the local home owners association HOA to receive approval of the CSM solution Take severa...

Страница 28: ... 320 subscriber module G1_CCSMfrtpanelview eps Figure 1 7 Connectorized CSM 320 rear view subscriber module G1_CCSM_rearviewconn ext The PMP 320 Connectorized Cluster Subscriber Module CSM or also known as the Customer Premise Equipment CPE or the Subscriber Module SM is the device that extends the broadband network or internet services to the end user through communication with the PMP 320 AP The...

Страница 29: ...ered as is used for the AP Mount the Connectorized CSM as high off the ground as possible to minimize theft Communicate to the end user that they are responsible for the loss damage to the Connectorized CSM while in their care Route and hide the ENET cables against the house following local installation codes This extra effort lowers the chance of a new home owner taking down the Connectorized CSM...

Страница 30: ...he instructions and procedures needed to connect the antenna brackets connect the AP radio antenna to the antenna cable the unit mount the unit to a pole mounting fixture or tower ground the unit connect surge suppression PMP320HDW2v1 2 1 JUL 2010 Preliminary ...

Страница 31: ......

Страница 32: ...nfiguring sections of the PMP 320 Administration and Configuration 2 Assemble the AP radio antenna and brackets and physically install it using Procedure 2 1 A CMM4 is typically installed at the same time if not previously installed 3 Cable the AP to the CMM4 and ground it to Protective Earth PE using Procedure 2 2 4 This phase can also include cabling to backhauls or running terrestrial feeds 5 C...

Страница 33: ...a Scissors bracket 1 Top pipe clamp assembly 1 Bottom pipe clamp assembly 1 2 24 inch spacer 2 2 36 inch spacer 1 5 16 18 x 3 5 inch hex pivot 3 bolt 5 16 18 inch split lock 3 washer 5 16 18 flat washer 3 5 16 18 hex nut 3 Attaching AP to Antenna M6 carriage bolt 2 M6 split lock washer 2 M6 flat washer 2 M6 hex nut 2 Attaching pipe clamps to pipe 3 8 16 inch split lock washer 4 3 8 16 inch flat wa...

Страница 34: ...dentification TOP PIPE CLAMP ASSEMBLY BOTTOM PIPE CLAMP ASSEMBLY Longer Bracket 3 8 16 Hex Nut 3 8 16 Split Lock Washer 3 8 16 Lock Washer 3 8 16 Hex Nut 3 8 16 Split Lock Washer 3 8 16 Lock Washer Figure 2 2 AP and antenna parts with scissors bracket Pole Is Shown For Reference Antenna Radio Secured on Antenna DIV connector MAIN connector Ethernet ...

Страница 35: ... brackets to the AP and attach the radio to the antenna These steps are performed before the AP is mounted on the pole Required Tools Two inch wrenches 9 16 inch wrench and inclinometer 10mm socket wrench Torque Requirements 3 8 16 pipe clamp hardware to 9 ft lbs 12 2 N m 5 16 18 mount hardware 10 ft lbs 13 5 N m M6 hardware 7 ft lbs 9 5 N m Procedure 2 1 Assemble the AP and antenna for pole mount...

Страница 36: ...m a parts check to ensure all parts are present 2 Connect the pipe clamp assembly brackets to the antenna NOTE Determine between the two pipe clamp assemblies which bracket has the longer bracket bar The bracket with the longer bar is attached to the bottom of the antenna The bracket with the shorter bar is used for the top of the antenna and connected to the scissors downtilt bracket Continued ...

Страница 37: ...P ASSEMBLY Longer Bracket 3 8 16 Hex Nut 3 8 16 Split Lock Washer 3 8 16 Lock Washer 3 8 16 Hex Nut 3 8 16 Split Lock Washer 3 8 16 Lock Washer 3 Using the longer bracket pipe clamp Bottom pipe clamp assembly attach the bracket to the bottom of the antenna using a 5 16 18 x 3 5 inch hex pivot bolt 5 16 hex nut Spacer 2 24in 5 16 8 x 3 5in Hex Pivot Bolt 5 16 8 Hex Nut 5 16 8 Split Lock Washer 5 16...

Страница 38: ... the antenna See Detail A 5 16 8 Split Lock Washer Outside 5 16 8 Hex Nut 5 16 8 Flat Washer 5 16 8 x 3 5in Hex Pivot Bolt Spacer 2 36in Detail A Inverted Scissor Mount 5 Using the bracket with the shorter bar attach the downtilt scissor bracket pointing up inverted scissor mount to avoid physical interference between the bracket and the radio housing Connect the scissor bracket to the short pipe ...

Страница 39: ... 5in Hex Pivot Bolt 5 16 8 Split Lock Washer Use a level inclinometer to tilt of the antenna when installing at the site The scissor bracket has degree markings from 0 to 15 on the bracket but it is recommended for accuracy to use a level 6 Connect the radio to the antenna by sliding it into the captive space Radio 2X M6 Hex Nut 2X M6 Lock Washer 2X M6 Flat Washer NOTE Slide Radio into captive spa...

Страница 40: ...2 10 PMP320HDW2v1 Preliminary JUL 2010 Assembling the AP and connecting the antenna Chapter 2 AP Hardware Installation Procedure 2 1 Assemble the AP and antenna for pole mounting Continued Continued ...

Страница 41: ...rque the M6 nut 7 ft lbs 9 5 N m The unit is shown away from the antenna in order to illustrate bolt locations Pole Is Shown For Reference Antenna Radio M6 Carriage Bolt M6 Flat Washer M6 Lock Washer M6 Hex Nut M6 Carriage Bolt M6 Flat Washer M6 Lock Washer M6 Hex Nut DIV Connector MAIN Connector 8 Connect the cable labeled MAIN to the antenna connector labeled MAIN with no label to the antenna co...

Страница 42: ...rth Ground cable assembly and connection Standard installation practices apply which include use of shielded Ethernet cable for all infrastructure cabling use of drip loops at any point where the cable changes direction extra cable a splice loop is provided for future use at any termination ensuring the tower or structure is fully grounded Protective Earth PE use water tight tape followed by elect...

Страница 43: ...ormly non conducting on all connections and in all RJ 45 Ethernet connectors The best practice is to use enough grease to fill the RJ 45 female connector and then insert the RJ 45 male connector and push the grease further into the unit and around the RJ 45 connector Excess grease can be wiped over the connector area to provide some resistance to water ingress around the connector Connect the Ethe...

Страница 44: ...e assembly and connection Procedure 2 2 Cabling and grounding the AP Continued 3 Run a 10 AWG ground strap from the ground lug on the AP to known good ground Protective Earth PE AP Ground Lug Ground the radio to the tower 4 Be sure to reattach the bottom cover of the AP connection cover ...

Страница 45: ...ower is on This LED indicates that the board is powered on SYN 1 D13 Synchronization indicator this indicator is on whenever the AP is synchronized with the GPS or when ever the GPS is not used at all SES 2 D12 Not used but is always ON LNK 5 D9 GMAC Ethernet the LED is on when the GMAC Ethernet link is up ACT 4 D10 Activity indicates activity on the ENET port GPS 3 D11 GPS pulse indicator this LE...

Страница 46: ...power lines The network planner should provide the antenna pattern information for the installation The network is planned from true north 0 degrees Use a compass to ensure there is no overlap of the antennas as they are installed Figure 2 4 Mounting the AP to the tower AP Communications Bldg Cable Tray BT 0781S XXX BT 0781S XXX AP Grounded to Tower with 10AWG wire Network Switch or Router CMM4 Dr...

Страница 47: ...are This figure shows the GPS near the top of the AP unit For installation information about the GPS refer to Installing the GPS Antenna on page 3 7 Procedure 2 3 Attaching the AP assembly to a pole 1 Using standard work and safety practices for tower climbing connect the assembled unit assembled antenna brackets and radio to a pole mounting fixture or a tower The unit must be mounted to avoid acc...

Страница 48: ...enna pattern information for the installation The network is planned from true north 0 degrees Use a compass to ensure there is no overlap of the antennas as they are installed Tighten the hex nut to 10 ft lbs 13 5 N m after the AP has been aligned to the optimum downtilt position 3 Connect the Ethernet cable from the AP to the CMM4 port controller There are up to 14 ports in one CMM4 switch but o...

Страница 49: ...cific to the switch part number GND Black REDUNDANT V Red 29 V REDUNDANT 29 V 56 V 56 V INPUT INPUT INPUT INPUT GND GND V GND GND V V GND V GND V GND V GND PE CMM4 CONTROLLER Power Port View EXTERNAL PROTECTIVE EARTH GROUND 29 V 56 V EtherWAN Switch OUTPUT Red OUTPUT Green RS232 Ethernet Port View OR Red Green 29 V 56 V 1000 BaseT 1000 BaseT DEFAULT NORMAL OUTPUT OUTPUT AUX SYNC ETHERN TOGGLE SHIE...

Страница 50: ...s on an Ethernet link without degrading the link The equivalent of a 600SSD is built into each of the 8 ports on a CMM4 and counts as one of the four As an example a typical installation might have properly grounded 600SSD units within 3 ft 1 m of each AP and additional properly grounded 600SSD units on each Ethernet cable mounted outside at the point of cable entry to a telecommunications hut tha...

Страница 51: ...JUL 2010 Preliminary AP Hardware Installation complete Chapter 2 AP Hardware Installation 2 20 PMP320HDW2v1 ...

Страница 52: ...nary JUL 2010 Chapter 3 CMM4 Hardware Installation The CMM4 consists of three subsystems the CMM4 enclosure and controller board power supplies an EtherWAN switch mounted in the CMM4 enclosure PMP320HDW2v1 3 1 ...

Страница 53: ...0SSD AC Power SGPN4076 200SSB Tower Ground Earth Ground Tower NOTE The L COM surge suppressor is used if the Gigabit Ethernet port is used in the CMM4 The L COM when used is installed either in the CMM4 cabinet or installed inside the communications building This figure shows the GPS near the top of the AP unit For installation information about the GPS refer to Installing the GPS Antenna on page ...

Страница 54: ... and industry best practices and follow the specific guidelines in this document If the CMM4 is being installed on a tower instead of a communications hut the operator will have to calculate the wind loading on the tower for the addition of the CMM4 Avoiding Hazards Use simple precautions to protect staff and equipment Hazards include exposure to RF waves lightning strikes and power surges This se...

Страница 55: ...al purposes ensure that your network conforms to applicable country and local codes such as the NEC National Electrical Code in the U S A If you are uncertain of code requirements engage the services of a licensed electrician In particular many codes require that wired electrical devices like the 56 VDC power supply either terminate in a plug connection or be wired with an on off switch and not be...

Страница 56: ...e products carefully inspect all shipping boxes for signs of damage If you find damage immediately notify the transportation company As you unpack the equipment verify that all the components that you ordered have arrived Save all the packing materials to use later as you transport the equipment to and from installation sites ...

Страница 57: ... The physical installation of the CMM4 includes the following physically install the CMM on the tower or near the communications hut physically install the GPS unit included with the CMM4 does not have to be ordered separately physically install the surge suppressors cable the following CMM4 components GPS Power ENET 600SSD surge suppressor 200SB surge suppressor L COM surge suppressor if the Giga...

Страница 58: ...o 20 degrees Do not install the GPS as the highest object at the site Information on GPS cable planning ordering and design is covered in GPS Coax Cable on page 3 8 The following information describes the recommended tools and procedures to mount the GPS antenna Recommended Tools for GPS Antenna Mounting The following tools and materials are needed for mounting the GPS antenna 3 8 inch nut driver ...

Страница 59: ... mounted 3 Attach the GPS unit to the bracket using 4 screws 4 Place the U bolts provided around the pole 5 Slide the GPS antenna bracket onto the U bolts 6 Slide the ring washers provided onto the U bolts 7 Slide the lock washers provided onto the U bolts 8 Use the nuts provided to securely fasten the bracket to the U bolts 9 Connect the GPS coax cable to the female N connector on the GPS antenna...

Страница 60: ... Alternatively equivalent cables may be procured by the operator fabricated by the operator in a depot or fabricated at site using Up to 100 feet 30 4 meters of LMR200 coaxial cable 2 Times Microwave N male connectors Times Microwave P N TC 200 NM or equivalent connectors NOTE The CMM4 has a female N type coax connector on the outside of the enclosure whereas the CMM micro has a female BNC type co...

Страница 61: ... Although the output of the power supply is 29 VDC or 56 VDC the power rating classifies the converter as a Class 2 electric device For this reason whenever you work on power in the CMM4 you must first disconnect the DC supply from the AC power source Select the appropriate procedure to install the power supply for the CMM4 Directions are provided for a 56 VDC power supply and a procedure on how t...

Страница 62: ... and lever the screwdriver away from the main cage clamp hole 1 2 3 N L Input The AC line cord is not provided with the hardware 6 Terminate the other end of the AC cable to a country specific AC connector or wire to a switch in accordance with local electrical codes AUX 2 AUX 1 PMP 320 Hardware Installation 56 VDC Power Supply Installation Procedure 3 2 Installing a 56 VDC Power Supply for the CM...

Страница 63: ...stallation If the PMP 320 will be co located with PMP 100 equipment on the same CMM4 refer to the Cluster Management Module 4 User Guide at http motorola wirelessbroadbandsupport com for additional information on how to install the 30 VDC power supply and the 1000 Ohm 5 W resistor that must be installed along with that power supply ...

Страница 64: ...ted side of the 200SSB to the AC power supply SGPN4076 connect the protected side of the 600SSD to the network switch or router in the communications hut add drip loops at any point in the cabling where the cable changes direction NOTE Additional L COM considerations during installation if the CMM4 unit is mounted on the antenna and is located more that three feet away from the communications hut ...

Страница 65: ...t the desired location Drill a 3 4 inch 18 mm hole through the wall of the communications hut at the desired location 5 Connect the Ethernet cable from the network or switch router from the communications hut to the Ethernet port on the 600SSD surge suppressor 6 Use dielectric grease which is uniformly non conducting on all connections and in all RJ 45 Ethernet connectors The best practice is to u...

Страница 66: ...ession unit inside the CMM4 housing Be careful not to place the surge suppressor in the unit as to crush any cables in the CMM4 unit or cables going through the cable glands 5 Connect the Gigabit Ethernet connection from the CMM4 to the L COM Ethernet connector 6 Connect the Ethernet cable from the L COM surge suppressor and feed the cable through the cable gland on the CMM4 and connect to the swi...

Страница 67: ...Hardware Installation Procedure 3 4 L COM surge suppressor installation Continued 11 Connect the Ethernet cable from the CMM4 to the Ethernet port on the surge suppressor port 12 Connect the surge suppressor to the Earth Ground 13 Place the cover on the L COM unit and attach the L COM cover ...

Страница 68: ...uster Manager Module located at http motorola wirelessbroadbandsupport com software When performing the installation of the CMM4 unit remember to install the CMM4 outside the communications hut whenever possible do not mount the power supply inside the CMM4 enclosure use 200SS for all the DC cables powering the CMM4 label all the CMM4 connections do not accidentally toggle the default switch on th...

Страница 69: ...witch from the physical units after you discover a CMM4 and its switch use these MAC addresses for moving the switch to the place in your Prizm or Wireless Manager network view where the CMM4 was discovered always maintain a record that associates these two MAC addresses CAUTION When an EMS discovers an EtherWAN switch in your network it can t tell which CMM4 the switch is associated with nor can ...

Страница 70: ... be mounted 3 If the support structure is a wall use screws or bolts neither is provided to attach the flanges to the wall an irregular shaped object use adjustable stainless steel bands provided to attach the CMM4 to the object a pole that has an outside diameter of 1 25 to 3 inches 3 to 8 cm use a toothed V bracket provided to attach the V bracket to the pole Then attach the CMM4 flanges to the ...

Страница 71: ...UT specific to the switch part number GND Black REDUNDANT V Red 29 V REDUNDANT 29 V 56 V 56 V INPUT INPUT INPUT INPUT GND GND V GND GND V V GND V GND V GND V GND PE CMM4 CONTROLLER Power Port View EXTERNAL PROTECTIVE EARTH GROUND 29 V 56 V EtherWAN Switch OUTPUT Red OUTPUT Green RS232 Ethernet Port View OR Red Green 29 V 56 V 1000 BaseT 1000 BaseT DEFAULT NORMAL OUTPUT OUTPUT AUX SYNC ETHERN TOGGL...

Страница 72: ...w the diagram inside the door of the CMM4 Refer to Figure 3 5 2 The inserts in the gland openings of the CMM4 have precut holes 3 Route Ethernet cables through the cable gland connectors to the Ethernet ports inside the CMM4 cabinet see the grey cables in the illustration Stagger the cables as shown in the figure to make it easier to feed them through the gland Continued ...

Страница 73: ...nections If the CMM4 is mounted inside a building or communications hut a Motorola 600SSD surge suppressor model number 600SSC or later should be mounted outside the building or communications hut on each line at the point of cable penetration to prevent over voltages and over currents from entering the building and potentially damaging other electronic equipment Terrestrial feeds over 100 Mbps 10...

Страница 74: ...ct the black wire to V GND on the same 56 VDC terminal block 13 Plug the DC power supply into an AC receptacle AC mains NOTE The AC line cord is not provided with the hardware 14 Verify that the LEDs light PMP 320 Hardware Installation LED indicators Procedure 3 6 Cabling the CMM4 Continued mounted outside locate the PIDU in a weather tight enclosure within 3 ft 1 m of the CMM4 and install a Hyper...

Страница 75: ... in the building The following equipment mounted outside of a communications hut or building at the point where the cables penetrate the building is recommended Motorola 600SSD surge suppressors for Ethernet cables Motorola 200SS surge suppressors for DC cables A PolyPhaser DGXZ 06NFNF A surge suppressor for the coaxial cable from the GPS antenna Power Faults If excessive current is drawn on a por...

Страница 76: ...have been connected in this installation procedure refer to the located at http motorola wirelessbroadbandsupport com software Other Installation Considerations If two CMM4 devices are synchronized together the CMM4 that does not have a GPS needs to be set up via the GUI as a CMM slave device Refer to the CMM4 User guide located at http motorola wirelessbroadbandsupport com software ...

Страница 77: ...PMP320HDW2v1 3 47 JUL 2010 Preliminary Other Installation Considerations Chapter 3 CMM4 Hardware Installation 3 26 PMP320HDW2v1 ...

Страница 78: ...Preliminary JUL 2010 Chapter 4 Cables ...

Страница 79: ...own in Table 4 1 These wire sizes support up to 8 radios 30 VDC or 56 VDC radios at up to 100 m 328 ft Ethernet cable length from the CMM4 Table 4 1 Wire size for CMM4 DC cable DC Power Cord Length Wire Gage Up to 90 ft 3 25 m 12 AWG 4 mm2 91 145 ft 26 45 m 10 AWG 6 mm2 146 230 ft 46 70 m 8 AWG 10 mm2 For supporting 8 PMP 54400 APs or PTP 54200 BHs which are 12 W 30 VDC radios reduce either the ma...

Страница 80: ...er Description Infrastructure Ethernet cable Infrastructure Ethernet cable for plenums BT 0781S XXX RJ 45 to RJ 45 straight shielded UV resistant Ethernet cable using outdoor STP Cat 5e cable lower cost than plenum rated available only in black BT 0562S XXX RJ 45 to RJ 45 straight shielded UV resistant plenum rated Ethernet cable using outdoor STP Cat 5e cable available in beige blue grey or white...

Страница 81: ...nded Ethernet Cables Pin Color 1 white orange 2 orange 3 white green 4 blue 5 white blue 6 green 7 white brown 8 brown Figure 4 2 Pin 1 Location diagram Lock ta b unde rneath Pin 1 Bulk unterminated Ethernet cable can be ordered from Best Tronics as bulk cable CA 0287S shielded plenum rated CA 0367S lower cost shielded non plenum rated ...

Страница 82: ...ther The ability to have one GPS antenna support two CMMs Warm spare redundant sync Pinouts for the CMM sync cable are shown in the following figures Figure 4 4 shows the location of Pin 1 relative to the lock tab on the connector NOTE The CMM sync cable used to connect two CMMs for sync purposes has different pinouts than the straight through sync cable used to connect a remote AP to an SM or an ...

Страница 83: ...PMP320HDW2v1 4 53 Preliminary JUL 2010 CMM Sync Cable Chapter 4 Cables Figure 4 3 CMM sync cable pinouts Figure 4 4 CMM sync cable pinouts Lock tab is on other side Pin 1 ...

Страница 84: ...power up connection IP connectivity alignment correction CAUTION The orientation of the CSM when installed is important The face of the CSM with the Motorola logo must be pointing in the direction of the antenna facing outwards from the building The Ethernet connector must be oriented so it is on the bottom right corner of the CSM Figure 5 1 CSM CPE 320 Identification Canopy CSM 320 Ethernet Conne...

Страница 85: ......

Страница 86: ...ter Ground wire of sufficient length to run between the CSM and the home ground point NOTE It is recommended that the ground wire be a 6 AWG solid copper wire It is recommended that if a ground rod is used it should be an 8 ft 2 5m copper rod Most buildings have an existing ground rod outside at the main power connection site If desired a rod can be installed into the ground outside the building a...

Страница 87: ...M on the north side of the building After determining the optimal side of the building select an CSM mounting point at a high location is unlikely to be touched by user passer on the building such as under the eaves Components shipped with the CSM Locate the components shipped with the CSM device The parts list for the CSM installation consists of the following items Table 5 1 CSM parts list Compo...

Страница 88: ...acket Top Mounting Bracket Base Mounting 4X M4 x 16MM Bolt 4X M4 Split Washer 4X M4 Washer M8 Nut Middle Mounting bracket 2X M8 Nut 4X M8 Split Washer 4X M8 Washer M8 Split Washer M8 Washer 2X M8 x 100 MM Bolt Mounting Pole Reference Cabling Overview The following items are not supplied with the system Ground wire Grounding rod Outdoor power Ethernet cable Ethernet cable Computer NIC Figure 6 4 il...

Страница 89: ...llation Cabling Overview Figure 5 3 CSM mounted to a wall Building s Roof CPE Bracket assembly attached to building s exterior Subscriber s Computer CPE Power Ethernet cable Dsine Surge Suppressor Ethernet cable not supplied Ground wire not supplied to household grounding point ...

Страница 90: ...nstallation location on the building NOTE The CSM can be mounted either directly on the building or on a pole Installing the CSM Chapter 5 CSM Hardware Installation Installing the CSM This section describes how to find an appropriate installation location for the CSM and how to install the CSM on the building Selecting a location for the CSM Determine the optimum installation location for the CSM ...

Страница 91: ...he CSM to a pole using the wall bracket and pole clamp of the bracket assembly 3 Adjust the vertical and horizontal tilt of the CSM so that it can obtain the best signal 4 Fully tighten the bracket assembly into the desired position Completing the mounting bracket assembly Perform the following procedure to complete the mounting bracket assembly Refer to Figure 6 3 to reference the brackets and th...

Страница 92: ...olt jam is facing the ground 10 Guide the rest of the bolt through the arch of the wall bracket 11 Slide a tooth lock washer at the end of the hex bolt 12 Align the hole on the tab of the bracket arm with the end of the bolt 13 Slide the tab of the bracket arm onto the bolt and then place a flat washer over the end of the bolt 14 Tighten the end of the bolt with a hex nut Leave the hex nut loose e...

Страница 93: ...tion when drilling through the wall of the building Ensure that there are no power lines gas lines water lines or data lines in the wall at the desired location where the drilling takes place 3 After the holes are drilled into the building drive the screws through the holes on the wall bracket and into the building While attaching the bracket assembly to the wall ensure that the bottom of the CSM ...

Страница 94: ...best signal strength NOTE This alignment procedure assumes that the installer has reviewed the site interference values collected for the area of the installation The bolts connecting the two pole wall brackets to the bracket arm are not yet fully tightened Hence use the bracket arm to adjust the vertical and horizontal tilt of the CSM This adjustment helps the CSM to obtain the strongest signal f...

Страница 95: ...est signal from the service provider tighten all the bolts on the mounting bracket assembly Once the screws are tightened the CSM will no longer move sideways nor up and down 6 Log out of the CSM GUI once optimal signal strength is achieved After completing the alignment and mounting of the CSM on the outside of the building proceed with the installation procedures for the subscriber Ethernet surg...

Страница 96: ...thernet cable and RJ 45 plug This weatherized cable connects to the ENET connector of the CSM Figure 5 4 Ethernet cable weather protection assembly 1 Strip cable sheath 2 Insert the screw nut into the housing 3 Insert the seal at the back end of the housing 7 7 Recommended wire Gauge 24AWG Screw Nut Seal 4 Insert the cable all the way through Cable 5 Crimp the RJ45 plug Crimp the RJ45 plug 6 Inser...

Страница 97: ...r Excess grease can be wiped over the connector area to provide some resistance to water ingress around the connector 3 Wrap a drip loop in the cable at any point where the cable changes direction 4 Measure the cable so it will span from the CSM to the surge suppressor box 5 Fasten the cable to the building according to local building codes NOTE Cables that move in the wind can be damaged impart v...

Страница 98: ...here the drilling takes place Procedure 5 8 Running cables through the wall of the building 1 CAUTION Follow local building codes for penetrating buildings Observe caution when drilling through the wall of the building Ensure that there are no power lines gas lines water lines or data lines in the wall at the desired location Drill a 3 4 inch 18 mm hole through the wall at the desired location 2 D...

Страница 99: ...e Surge Suppressor on page 6 13 Refer to Figure 6 7 3 Pack both of the 600SSD surge suppressor Ethernet jacks with dielectric grease 4 Include a splicing loop in the Ethernet cable from the CSM extra cable to allow future repositioning or reconnectorization and position and secure the Ethernet cable with UV resistant wire ties or other locally approved fasteners so it forms a drip loop so water dr...

Страница 100: ...ER DATA POWER DATA OUT IN PORT AC Connecting the ground wire The CSM must be grounded to a household ground point or to a grounding rod according to the applicable electrical code Equipment grounding practices vary with local building codes and established practices of the service provider Following is the CSM grounding procedure as recommended by Motorola The ground wire must be a minimum of 18 A...

Страница 101: ...ehold ground point according to the applicable electrical code Attach all wires to the building using electrical staples Use drip loops as required Use the following procedure to ground the CSM at the residence premises Procedure 5 10 Grounding the CSM 1 Wrap the AWG 10 6mm2 copper ground wire around the ground post of the CSM 2 Remove the cover of the 600SSD surge suppressor 3 Wrap the AWG 10 6mm...

Страница 102: ... of the CSM power injector 3 Use a standard category 5e Ethernet cable to connect the computer to the jack labeled computer on the power supply NOTE The cable to the CSM provides both power and Ethernet connection It is not pin or voltage compatible with IEE std 802 3af 2003 power over Ethernet 4 The power cord uses standard household power Plug the power cord in the AC power source NOTE The AC li...

Страница 103: ...tenna cables to the unit ground the unit add surge suppression post power up connection IP connectivity alignment correction CAUTION The orientation of the CSM when installed is important The face of the CSM with the Motorola logo must be pointing in the direction of the antenna facing outwards from the building The Ethernet connector must be oriented so it is on the bottom right corner of the Con...

Страница 104: ...er supply and the Ethernet cable to the computer Chapter 6 Connectorized CSM Hardware Installation Figure 6 1 Connectorized CSM CPE 320 Identification G1_CCSMfrtpanelview eps Figure 6 2 Connectorized CSM CPE 320 Rear View Connectors G1_CCSM_rearviewconn ext ...

Страница 105: ... Ground wire of sufficient length to run between the CSM and the home ground point NOTE It is recommended that the ground wire be a 6 AWG solid copper wire It is recommended that if a ground rod is used it should be an 8 ft 2 5m copper rod Most buildings have an existing ground rod outside at the main power connection site If desired a rod can be installed into the ground outside the building afte...

Страница 106: ...orth of the building install the CSM on the north side of the building After determining the optimal side of the building select an CSM mounting point at a high location on the building such as under the eaves Components shipped with the CSM Locate the components shipped with the CSM device The parts list for the CSM installation consists of the following items Table 6 1 CSM parts list Component Q...

Страница 107: ... Bottom Mounting Bracket Top Mounting 4X M4 x 16MM Bolt 4X M4 Split Washer 4X M4 Washer M8 Nut M8 Split Washer M8 Washer Middle Mounting bracket 2X M8 x 100 MM Bolt 2X M8 Nut 4X M8 Split Washer 4X M8 Washer Mounting Pole Reference Cabling Overview The following items are not supplied with the system Ground wire Grounding rod Outdoor power Ethernet cable Ethernet cable Computer NIC Figure 6 4 illus...

Страница 108: ... CSM mounted to a wall Building s Roof CPE Bracket assembly attached to building s exterior Connectorized CSM antenna not shown Subscriber s Computer CPE Power Ethernet cable Dsine CPE Bracket assembly attached to building s exterior Surge Suppressor Ethernet cable not supplied Ground wire not supplied to household grounding point ...

Страница 109: ...M installation location on the building NOTE The CSM can be mounted either directly on the building or on a pole PMP 320 Hardware Installation Installing the CSM Installing the CSM This section describes how to find an appropriate installation location for the CSM and how to install the CSM on the building Selecting a location for the CSM Determine the optimum installation location for the CSM bef...

Страница 110: ...ssembly 2 Mount the CSM to a pole using the wall bracket and pole clamp of the bracket assembly 3 Adjust the vertical and horizontal tilt of the CSM so that it can obtain the best signal 4 Fully tighten the bracket assembly into the desired position Completing the mounting bracket assembly Perform the following procedure to complete the mounting bracket assembly Refer to Figure 6 3 to reference th...

Страница 111: ... jam is facing the ground 10 Guide the rest of the bolt through the arch of the wall bracket 11 Slide a tooth lock washer at the end of the hex bolt 12 Align the hole on the tab of the bracket arm with the end of the bolt 13 Slide the tab of the bracket arm onto the bolt and then place a flat washer over the end of the bolt 14 Tighten the end of the bolt with a hex nut Leave the hex nut loose enou...

Страница 112: ...bserve caution when drilling through the wall of the building Ensure that there are no power lines gas lines water lines or data lines in the wall at the desired location where the drilling takes place 3 After the holes are drilled into the building drive the screws through the holes on the wall bracket and into the building While attaching the bracket assembly to the wall ensure that the bottom o...

Страница 113: ...enna connectors is 18 inches 1 ft and 6 in Refer to the Chapter titled Installing Antennas for additional information regarding antenna installation procedures Figure 6 5 Connectorized CSM antenna cable connector location G1_Ccsmantennaconnid eps Procedure 6 6 Connecting the Antenna Cables to the Connectorized CSM when using an Omni Antenna 1 Verify that the length between the CSM and the Omni ant...

Страница 114: ...d CSM when using an Diagonal Polarized Antenna 1 Using a 50 ohm low loss cable with an N type connector connect the N type connector to the V polarity connector of the antenna to the CSM N type connector Refer to Figure 6 5 for cable connection location on the CSM 2 Using the other 50 ohm cable connect the N type connector to the H polarity connector of the antenna to the CSM N type connector ...

Страница 115: ...rnet cable and RJ 45 plug This weatherized cable connects to the ENET connector of the CSM Figure 6 6 Ethernet cable weather protection assembly 1 Strip cable sheath 2 Insert the screw nut into the housing 3 Insert the seal at the back end of the housing 7 7 Recommended wire Gauge 24AWG Screw Nut Seal 4 Insert the cable all the way through Cable 5 Crimp the RJ45 plug Crimp the RJ45 plug 6 Insert t...

Страница 116: ...ale connector and push the grease further into the unit and around the RJ 45 connector Excess grease can be wiped over the connector area to provide some resistance to water ingress around the connector 3 Wrap a drip loop in the cable at any point where the cable changes direction 4 Measure the cable so it will span from the CSM to the surge suppressor box 5 Fasten the cable to the building accord...

Страница 117: ...e the drilling takes place Procedure 6 9 Running cables through the wall of the building 1 CAUTION Follow local building codes for penetrating buildings Observe caution when drilling through the wall of the building Ensure that there are no power lines gas lines water lines or data lines in the wall at the desired location Drill a 3 4 inch 18 mm hole through the wall at the desired location 2 Draw...

Страница 118: ... Ground the Surge Suppressor on page 6 13 Refer to Figure 6 7 3 Pack both of the 600SSD surge suppressor Ethernet jacks with dielectric grease 4 Include a splicing loop in the Ethernet cable from the CSM extra cable to allow future repositioning or reconnectorization and position and secure the Ethernet cable with UV resistant wire ties or other locally approved fasteners so it forms a drip loop s...

Страница 119: ...DATA POWER DATA OUT IN PORT AC Connecting the ground wire The CSM must be grounded to a household ground point or to a grounding rod according to the applicable electrical code Equipment grounding practices vary with local building codes and established practices of the service provider Following is the CSM grounding procedure as recommended by Motorola The ground wire must be a minimum of 18 AWG ...

Страница 120: ...o the household ground point according to the applicable electrical code Attach all wires to the building using electrical staples Use drip loops as required Use the following procedure to ground the CSM at the residence premises Procedure 6 11 Grounding the CSM 1 Wrap the AWG 10 6mm2 copper ground wire around the ground post of the CSM 2 Remove the cover of the 600SSD surge suppressor 3 Wrap the ...

Страница 121: ...ector 3 Use a standard category 5e Ethernet cable to connect the computer to the jack labeled computer on the power supply NOTE The cable to the CSM provides both power and Ethernet connection It is not pin or voltage compatible with IEE std 802 3af 2003 power over Ethernet 4 The power cord uses standard household power Plug the power cord in the AC power source NOTE The AC line cord is not provid...

Страница 122: ...Preliminary JUL 2010 Connecting the power supply and the Ethernet cable to the computer Chapter 6 Connectorized CSM Hardware Installation 6 20 PMP320HDW2v1 ...

Страница 123: ...JUL 2010 Preliminary Chapter 7 Connectorized CSM Antenna Installation Instructions PMP320HDW2v1 7 1 ...

Страница 124: ...8 GHz Omni Directional Base Station Antenna This section provides installation procedures for both types of antennas Dual Polarization Dual Slant Subscriber Antenna The Dual Polarization Dual Slant antenna features dual slant when it is mounted diagonally It also offers stable performance with 22 dBi of gain compact size allowing easy blending in any environment mount hardware that allows for quic...

Страница 125: ... 12 Cross Polarization max ETSI TS3 Front to Back Ratio max ETSI TS3 Port to Port Isolation typ 35 dB Input power max 10 Watt Input Impedance 50 Ohm Lightning Protection DC Grounded Table 7 2 Dual Polarized Dual Slant Subscriber Antenna Mechanical Specifications Specification Value Dimensions HxWxD 370 x 370 x 40 mm 14 5 x14 5 x1 6 Weight 2 1 kg Connector 2x SMA Female or 2x N Type Female Back Pla...

Страница 126: ...to IEC 68 2 11 Ice and Snow 25mm radial survival Service Life 10 years The Standard Compliance of the Dual Polarized Dual Slant Subscriber Antenna is ETSI TS3 Parts List Table 7 4 Dual Polarized Dual Slant Subscriber Antenna Parts List Quantity Description 1 Pole 1 inch to 4 inches not supplied 1 MNT 22 1 1 MNT 22 2 1 MNT 22 4 1 MNT 22 3 4 5 16 Helical spring lock washers 4 5 16 plain washer 2 5 1...

Страница 127: ...tion G1_antassemblyparts eps Tools The following tools are needed for the antenna mounting bracket assembly Torque driver 30 in lbs Antenna Mounting Instructions Use the following procedure to mount the Dual Polarized Dual Slant Subscriber Antenna Figure 7 3 Dual Polarized Dual Slant Subscriber Antenna Rear View for Mounting Assembly G1_antassemblyrearview eps ...

Страница 128: ...ssembly from step 3 Use a 5 16 inch helical spring lock washer a 5 16 inch plain washer a 5 16 18 x 1 25 inch hex cap screw and a 5 16 18 hex nut Leave the assembly loosely tightened Do not torque the nuts at this step 5 Locate the area of the pole to mount the antenna and place the bottom pole mounting bracket with the rest of the assembly on the pole 6 Attach the top pole bracket part number MNT...

Страница 129: ...on Specification Value Frequency range 3 3 3 8 GHz GAIN typ 9 5 dBi 3 4 3 8 9 dBi 3 3 3 4 VSWR max 2 1 Polarization Linear Vertical 3 dB Beam Width H Plane typ Omni Directional 3 dB Beam Width E Plane typ 10 Input power max 50 Watt Input Impedance 50 Ohm Table 7 6 Omni Directional Base Station Antenna Mechanical Specification Specification Value Dimensions HxDia 470 x 66 mm 18 5 x 2 5 Weight 350 g...

Страница 130: ... 60721 3 4 Wind Load 200 km h survival Flammability UL94 Water Proofing IP 65 Humidity ETS 300 019 1 4 EN 302 085 annex A 1 1 Salt Fog According to IEC 68 2 11 Ice and Snow 25mm radial survival Service Life 10 years Parts List Table 7 8 Omni Directional Base Station Antenna Pole Mounting Parts List Quantity Description 2 U brackets 4 Plain washers 4 Helical spring lock washers 4 Hex nuts Figure 7 ...

Страница 131: ...o securely fasten the antenna bracket to the U bracket 7 Repeat step 2 through step step 6 for the second bracket Repeat these steps for the second antenna 8 Connect the antenna to the connectorized CSM using the instructions in the Antenna Mounting Instructions Use the following procedure to mount the Omni Directional Base Station Antenna to a pole Note that two Omni Directional Base Station Ante...

Страница 132: ...Omni Directional Base Station Antenna Chapter 7 Connectorized CSM Antenna Installation Instructions 7 30 PMP320HDW2v1 Preliminary JUL 2010 ...

Страница 133: ...PMP320HDW2v1 7 31 JUL 2010 Preliminary Chapter 8 Regulatory Legal and Safety Notices ...

Страница 134: ...ications not expressly approved by the party responsible for compliance could void the user s authority to operate this equipment This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation IMP...

Страница 135: ... accordance with these instructions may cause harmful interference to radio communications If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment on and off the user is encouraged to correct the interference by one or more of the following measures Increase the separation between the affected equipment and the unit Connec...

Страница 136: ... cause harmful interference to radio communications If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment on and off the user is encouraged to correct the interference by one or more of the following measures Increase the separation between the affected equipment and the unit Connect the affected equipment to a power out...

Страница 137: ...an Union Notification The relevant Declaration of Conformity can be found at http motorola wirelessbroadbandsupport com doc php Equipment Disposal Please do not dispose of Electronic and Electric Equipment or Electronic and Electric Accessories with your household waste In some countries or regions collection systems have been set up to handle waste of electrical and electronic equipment In Europe...

Страница 138: ...or materials identified in the China Management Methods regulation Logo 2 means that the product may contain substances in excess of the maximum concentration value for materials identified in the China Management Methods regulation and has an Environmental Friendly Use Period EFUP in years fifty years in the example shown Logo 1 Logo 2 The Environmental Friendly Use Period EFUP is the period in y...

Страница 139: ...MC must be installed to provide a separation distance of at least 120 cm from all persons and must be not collocated or operating with any other antenna or transmitter Details of Exposure Separation Distances Calculations and Power Compliance Margins Limits and guidelines for RF exposure come from US FCC limits for the general population See the FCC web site at http www fcc gov the policies guidel...

Страница 140: ... APs they assume all APs are oriented in the same direction which is a worst case calculation They meet or exceed sustained exposure limits for the general population not just short term occupational exposure limits The calculated compliance distance d is overestimated because the far field equation models the antenna s as a point source and neglects the physical dimension of the antenna s Table 8...

Страница 141: ...PMP320HDW2v1 8 39 Preliminary JUL 2010 inches PMP 320 AP At least 50 cm approximately 20 inches ...

Страница 142: ...ns compilations derivative works including images partial copies and portions of updated works The Software is Motorola s or its supplier s confidential proprietary information This Software License Agreement does not convey to you any interest in or to the Software but only a limited right of use You agree not to disclose it or make it available to anyone without Motorola s written authorization ...

Страница 143: ... ABOVE LIMITATION MAY NOT APPLY TO YOU Maintenance and Support Motorola shall not be responsible for maintenance or support of the software By accepting the license granted under this agreement you agree that Motorola will be under no obligation to provide any support maintenance or service in connection with the Software or any application developed by you Any maintenance and support of the Relat...

Страница 144: ...te under these procedures have been unsuccessful ii the dispute claim or controversy involves intellectual property or iii interim relief from a court is necessary to prevent serious and irreparable injury to that party or to others General Illinois law governs this license The terms of this license are supplemental to any written agreement executed by both parties regarding this subject and the S...

Страница 145: ... Warranty in US Motorola US offers a warranty covering a period of 1 year from the date of purchase by the customer If a product is found defective during the warranty period Motorola will repair or replace the product with the same or a similar model which may be a reconditioned unit without charge for parts or labor ...

Страница 146: ...Y TO USE THE PRODUCT INCLUDING WITHOUT LIMITATION DAMAGES FOR LOSS OF BUSINESS PROFITS BUSINESS INTERRUPTION LOSS OF BUSINESS INFORMATION OR ANY OTHER PECUNIARY LOSS OR FROM ANY BREACH OF WARRANTY EVEN IF MOTOROLA HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES Some states do not allow the exclusion or limitation of incidental or consequential damages so the above exclusion or limitation may n...

Отзывы: