NICE7000 User Manual 7 Description of Function Codes
- 159 -
Bit
Function
Description
Default
Bit15
Higher/Low voltage
1.5s time detection
This function can be enabled when both higher voltage
and low voltage detections are performed on the door
lock circuit or safety circuit. When the time interval
between higher voltage and low voltage detection
exceeds 1.5s, the controller reports the door lock fault.
0
F6-11 Elevator function selection 3
Bit0
Fire emergency
display
There is hall call display after the elevator enters the fire
emergency state and returns to the fire emergency floor.
0
Bit1
Firefighter operation
display
There is hall call display when the elevator is in
firefighter operation state.
0
Bit2
Direction display at
micro-leveling
The adjustment direction is displayed during micro-
leveling adjustment.
0
Bit3
Determined direction
display in attendant
state
The determined direction is displayed at stop in
attendant state, even if there is no call.
0
Bit4
No direction display
at automatic stop
There is no direction display at automatic stop.
0
Bit5
Elevator lock at door
open
In the elevator lock state, the elevator keeps the door
open at the elevator lock floor.
0
Bit6
Display available at
elevator lock
In the elevator lock state, hall calls are displayed
normally.
0
Bit7
Elevator lock at any
floor hall call
The system enters the elevator lock state or returns to
the fire emergency floor at a hall call from any floor.
0
Bit8
Clear floor number
in advance
The displayed floor number is cleared before the
elevator reaches the destination floor.
0
Bit9
Clear floor number in
advance in attendant
state
The displayed floor number is cleared before the
elevator reaches the destination floor in attendant
running state.
Bit10
Displaying next
arriving floor number
The next floor to be arrived at is displayed during
elevator running.
0
Bit11
Blinking at arrival
The car display blinks when the elevator arrives at a
floor. The blinking advance time is set in F6-12.
0
Bit12
Door re-open during
door open delay
The door re-opens if the door open delay input is active
during door close.
0
Bit13
Door re-open after
car call of the
present floor
The door re-opens if the car call of the present floor is
valid during door close.
0
Bit14
Door re-open at door
close limit
The door re-opens if the door open signal is active at
door close limit.
0
Bit15
Reserved
-
0
Function Code
Parameter Name
Setting Range
Default
Unit
Property
F6-12
Blinking advance time
0.0–15.0
2.0
s
☆
Содержание NICE7000
Страница 1: ......
Страница 15: ......
Страница 16: ...1 Safety Information and Precautions ...
Страница 23: ...1 Safety Information and Precautions NICE7000 User Manual 22 ...
Страница 24: ...2 Product Information ...
Страница 34: ...3 Mechanical and Electrical Installation ...
Страница 71: ...4 Use of the Commissioning Tools ...
Страница 79: ...5 System Commissioning and Functions ...
Страница 102: ...5 System Commissioning and Functions NICE7000 User Manual 100 ...
Страница 103: ...6 Function Code Table ...
Страница 134: ...6 Function Code Table NICE7000 User Manual 132 ...
Страница 135: ...7 Description of Function Codes ...
Страница 205: ...8 Troubleshooting ...
Страница 224: ...8 Troubleshooting NICE7000 User Manual 222 ...
Страница 225: ...9 EMC ...
Страница 234: ...9 EMC NICE7000 User Manual 232 ...
Страница 237: ......