304
MTR
[Operation]
Caution
(1) Note that the MTR instruction directly operates on actual input and output.
The output that had been turned ON by the MTR instruction does not turn OFF when the MTR command turns OFF.
Turn OFF the specified output in the sequence program.
(2) The MTR instruction execution interval must be longer than the total of response time of input and output modules.
If the set interval is shorter than the value indicated above, an input cannot be read correctly.
If the scan time in a sequence program is short, select the constant scan and set the scan time longer than the total of
response time.