51
FX
3UC
Series Programmable Controllers
User’s Manual - Hardware Edition
1 Outline
1.8 Number of Input/Output Points and Maximum Number of Input/Output Points
1
O
utline
2
Exter
nal
D
im
en
sions
3
Ge
ne
ric
Speci
ficat
ions
4
Pow
er Suppl
y
Specif
icati
ons
5
Input
Spec
ific
ations
6
O
utput
Specif
icat
ions
7
Exam
pl
es
of
W
iri
ng
fo
r
Va
rious U
ses
8
Te
rm
inal B
lock
9
CC
-L
in
k/L
T
Ma
ste
r F
X
3UC
(LT
only)
10
D
ispl
ay m
odule
FX
3UC
(L
T only)
1.8.2
Maximum number of input/output points when CC-Link master is used
1. Calculation of maximum number of input/output points
The maximum number of available input/output points is as follows when the FX
3UC
-32MT-LT Ver. 2.20 or
later, FX
3UC
-
MT/D or FX
3UC
-
MT/DSS and CC-Link master block are used.
→
For the method of calculating the number of I/O points, refer to Subsection 1.8.1.
*1.
When seven 32-point type remote I/O stations are used, the number of CC-Link remote I/O points
reaches the maximum number.
The number of CC-Link points is calculated by the formula "32 points
×
number of stations" even when
remote I/O stations with less than 32 points are used.
For details, refer to the FX
2N
-16CCL-M User’s Manual.
2. Procedures for calculating number of input/output points based on example of system
configuration
For the main unit, input/output extension blocks and CC-Link remote I/O stations, the number of input/output
points and the total number of points are restricted.
≥
Maximum number of
input/output points
384 points
Maximum number
of points
controllable on
system
Number of input/
output points
+
Total number of
input/output points
(A)(B)(C)
Number of input/output occupied
points
(D) units
Number of points occupied by
special function units/blocks
+
CC-Link remote I/O
(E) stations
Total number of points obtained by
formula "number of remote I/O
stations
×
32 points" (The number is
multiplied by 32 points regardless of
the number of remote I/O points.)
For details, refer to Subsection 1.8.1.
(D): Number of input/output points occupied by special
function units/blocks
(E): Number of remote I/O stations (units) connected to CC-
Link master
×
8
points
×
32
points
(A): Number of input/output points of main unit
(B): Number of input/output points of input/output extension
blocks
(C): Number of remote I/O points of CC-Link/LT built-in
master(FX
3UC
-32MT-LT), FX
2N
-64CL-M, FX
2N
-16LNK-M.
-
-
Special
function unit
-
-
FX
2N
-16CCL-M
Output
extension
block
X000 to X017
Y000 to Y017
Main unit
(Example:
FX
3UC
-32MT/ )
X020 to X057
-
Input
extension
block
X060 to X117
-
Input
extension
block
Y020 to Y057
8 points
16/16
= 32 points
-
CC-Link network
Remote I/O
(8 points)
Remote I/O
(16 points)
Remote I/O
(32 points)
Remote I/O
(32 points)
Remote I/O
(32 points)
32/0
= 32 points
32/0
= 32 points
0/32
= 32 points
8 points
Number of
remaining points
Number of input/output points (128 points)
0 points
384 points
128
224 256
160
144
32 points
×
5 units = 160 points
Number of
remaining
points
Number of input/output points (excluding remote I/O points on CC-Link) + Number of
input/output occupied points
Up to 256 points
Number of input/output points occupied by special function units/blocks
Number of CC-Link input/output points
Up to 224 points
384 points or less in total
Содержание FX3UC Series
Страница 1: ...USER S MANUAL Hardware Edition FX3UC SERIES PROGRAMMABLE CONTROLLERS ...
Страница 2: ......
Страница 454: ...448 FX3UC Series Programmable Controllers User s Manual Hardware Edition F Discontinued models MEMO ...
Страница 457: ......