3 Generic Specifications/Installation Work
3.11 Connection to Input/Output Connector
3.11.2 Input/Output terminal block (European type) [FX
2NC
/FX
3UC
extension block]
1. Connection to terminal block
Terminal block type input/output extension blocks for FX
2NC
and terminal block type special function blocks
for FX
2NC
/FX
3UC
have the European type terminal block.
2. Electric wires
Compliant electric wires and tightening torque
3. Treatment of electric wire ends
Treat the ends of stranded wires and solid wires without coating or using bar terminals with insulating sleeve.
• Treatment of stranded wires and solid wires without coating
- Twist the ends of stranded wires tightly so that loose wires will not
stick out.
- Do not solder-plate the electric wire ends.
• Treatment using bar terminal with insulating sleeve
It may be difficult to insert the electric wire into the insulating sleeve
depending on the thickness of the electric wire sheath. Select the
electric wire referring to the outline drawing.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation
after installation or wiring work.
Failure to do so may cause electric shock.
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.22 and 0.25 N
•
m.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
Electric wire size
(stranded wire/solid wire)
Tightening
torque
End treatment
One electric wire 0.3mm
2
to 0.5mm
2
(AWG22 to 20)
0.22 to 0.25N•m
• Remove the coating of the stranded wire, twist
the core wires, and connect the wires directly.
• Remove the coating from the solid wire, and
connect the wire directly.
Two electric
wires
0.3mm
2
(AWG22)
Bar terminal with
insulating sleeve
0.3 mm
2
to 0.5 mm
2
(AWG22 to 20)
(Refer to the following outline
drawing of bar terminal.)
• Bar terminal with insulating sleeve
(recommended product)
AI 0.5-8WH : Phoenix Contact
• Caulking tool
CRIMPFOX ZA 3 : Phoenix Contact
(CRIMPFOX UD 6 : Phoenix Contact)
Manufacturer
Model names
Caulking tool
Phoenix Contact
AI 0.5-8WH
CRIMPFOX ZA 3
(CRIMPFOX UD 6)
9mm
(0.36")
•
Stranded wire/solid wire
8mm
(0.32")
Contact area
(Crimp area)
14mm(0.56")
2.6mm
(0.11")
Insulating sleeve
•
Bar terminal with insulating sleeve