208
FX
3UC
Series Programmable Controllers
User’s Manual - Hardware Edition
7 Examples of Wiring for Various Uses
7.8 Seven Segment with Latch [SEGL (FNC 74)/BCD (FNC 18)]
2. Output extension block
Example of program
Example of wiring
1) In the case of sink wiring
Use the sink only input, sink only output type main unit and a transistor output (sink only output) type
output extension block. The wiring example is the [FX
3UC
-32MT/D or FX
3UC
-32MT-LT] + output extension
block [FX
2NC
-16EYT].
2) In the case of source wiring
Use the sink/source common input, source only output type main unit and a transistor output (source only
output) type output extension block. The wiring example is the [FX
3UC
-32MT/DSS] + output extension
block [FX
2NC
-16EYT-DSS].
SEGL
M8000
D100 Y020
K1
10
3
10
2
10
1
10
0
1
2
4
8
10
3
10
2
10
1
10
0
1
2
4
Y020
COM1
Y021 Y022 Y023 Y024 Y025 Y026 Y027
8
Transistor output (sink)
*
COM1
FX
2NC
-16EYT
* Use a 7-segment display with a latch and a built-in BCD decoder.
Fuse
FX
3UC
-32MT/D
FX
3UC
-32MT-LT
Signal
-
Internal
circuit
7-segment display
+
Y
COM1
PLC
7-segment display to be used for sink wiring
(in the case of transistor output)
10
3
10
2
10
1
10
0
1
2
4
8
10
3
10
2
10
1
10
0
1
2
4
Y020
+V0
Y021 Y022 Y023 Y024 Y025 Y026 Y027
8
Transistor output (source)
*
+V0
FX
2NC
-16EYT-DSS
* Use a 7-segment display with a latch and a built-in BCD decoder.
Fuse
FX
3UC
-32MT/DSS
Signal
-
Internal
circuit
7-segment display
+
Y
PLC
+V0
7-segment display to be used for source wiring
(in the case of transistor output)