399
FX
3UC
Series Programmable Controllers
User’s Manual - Hardware Edition
12 Test Operation, Adjustment, Maintenance and Troubleshooting
12.6 Judgment by Error Codes and Representation of Error Codes
11
Mem
ory
Cass
ette/B
attery
12
Te
st
R
un,
M
aint
enanc
e,
Troubleshoot
ing
A
Ve
rs
ion
In
fo
rm
atio
n
B
Per
for
m
ance
Specif
icati
ons
C
S
pec
ia
l D
evices
(M80
00 -,
D
800
0 -)
D
In
str
uct
ion List
E
C
har
ac
te
r-code
F
D
isconti
nued
m
odels
PLC/PP communication error (D8062)
0000
-
No error
6201
Continues
operation
Parity, overrun or framing error
Check the cable connection between the
programming panel (PP)/programming device and
the PLC. This error may occur when a cable is
disconnected and reconnected during PLC
monitoring.
6202
Communication character error
6203
Communication data sum check error
6204
Data format error
6205
Command error
Serial communication error 1 [M8063 (D8063)]
0000
-
No error
6301
Continues
operation
Parity, overrun or framing error
• Inverter communication, computer link and
programming:
Ensure that the communication parameters are
correctly set according to their applications.
• N:N network, parallel link, etc.:
Check programs according to applications.
• Remote maintenance:
Ensure modem power is ON and check the
settings of the AT commands.
• Wiring:
Check the communication cables for correct
wiring.
6302
Communication character error
6303
Communication data sum check error
6304
Communication data format error
6305
Command error
6306
Communication time-out detected
6307
Modem initialization error
6308
N:N network parameter error
6312
Parallel link character error
6313
Parallel link sum error
6314
Parallel link format error
6320
Inverter communication error
Parameter error [M8064(D8064)]
0000
-
No error
6401
Stops
operation
Program sum check error
STOP the PLC, and correctly set the parameters.
6402
Memory capacity setting error
6403
Latched device area setting error
6404
Comment area setting error
6405
File register area setting error
6406
Special unit (BFM) initial value setting, positioning
instruction setting sum check error
6407
Special unit (BFM) initial value setting, positioning
instruction setting error
6409
Other setting error
Syntax error [M8065(D8065)]
0000
-
No error
6501
Stops
operation
Incorrect combination of instruction, device symbol
and device number
During programming, each instruction is checked. If
a syntax error is detected, modify the instruction
correctly.
6502
No OUT T or OUT C before setting value
6503
• No setting value after OUT T or OUT C
• Insufficient number of operands for an applied
instruction
6504
• Same label number is used more than once.
• Same interrupt input or high speed counter
input is used more than once.
6505
Device number is out of allowed range.
6506
Invalid instruction
6507
Invalid label number [P]
6508
Invalid interrupt input [I]
6509
Other error
6510
MC nesting number error
Error codes in shaded columns are added in FX
3UC
PLCs.
Error
code
PLC operation at
error occurrence
Contents of error
Action
Содержание FX3UC Series
Страница 1: ...USER S MANUAL Hardware Edition FX3UC SERIES PROGRAMMABLE CONTROLLERS ...
Страница 2: ......
Страница 454: ...448 FX3UC Series Programmable Controllers User s Manual Hardware Edition F Discontinued models MEMO ...
Страница 457: ......