154
FX
3UC
Series Programmable Controllers
User’s Manual - Hardware Edition
5 Input Specifications and External wiring
5.5 High-speed Counters (C235 to C255)
5.5.2
Input allocation of the High-Speed Counter
The high-speed counter numbers are allocated to the input terminals X000 to X007 as shown in the following
table.
When high-speed counters are used, the filter constant of the corresponding input numbers automatically
change (X000 to X005: 5
µ
s
*1
, X006 and X007: 50
µ
s).
The input terminals not allocated for high-speed counters can be used as general input terminals.
1. Allocation table
H/W: Hardware counter
S/W: Software counter
U: Up-count input
D: Down-count input
A: A-phase input B: B-phase input R: External reset input S: External start input
*1.
When the input terminals of the main unit receive pulses having a response frequency of 50k to
100kHz, wire the terminals as stated below.
-
The wiring length should be 5m (16’4") or less.
-
Connect a bleeder resistance of 1.5k
Ω
(1 W or more) to the input terminal, so that the load current
of the open collector transistor output on the mating device side to 20mA or more.
→
For the wiring, refer to Section 7.2.
*2.
When the comparison set/reset instructions (DHSCS, DHSCR, DHSZ and DHSCT) for high-speed
counters are used, the hardware (H/W) counters are switched to software (S/W) counters.
When the input signal logic is inverted by the reset input signal logic switching function (M8388 and
M8389), C253 is switched from a hardware counter to a software counter.
→
For the conditions under which it is handled as a software counter,
refer to Subsection 5.5.8.
*3.
When a special auxiliary relay is driven in a program, the input terminals and their associated
functions are switched.
→
For the procedures on switching to hardware counters, refer to Subsection 5.5.6.
Type of counter
Counter No.
Classifi-
cation
Input allocation
X000
X001
X002
X003
X004
X005
X006
X007
1-phase 1-count
input
C235
*1
H/W
*2
U/D
C236
*1
H/W
*2
U/D
C237
*1
H/W
*2
U/D
C238
*1
H/W
*2
U/D
C239
*1
H/W
*2
U/D
C240
*1
H/W
*2
U/D
C241
S/W
U/D
R
C242
S/W
U/D
R
C243
S/W
U/D
R
C244
S/W
U/D
R
S
C244(OP)
*3
H/W
*2
U/D
C245
S/W
U/D
R
S
C245(OP)
*3
H/W
*2
U/D
1-phase 2-count
input
C246
*1
H/W
*2
U
D
C247
S/W
U
D
R
C248
S/W
U
D
R
C248(OP)
*1*3
H/W
*2
U
D
C249
S/W
U
D
R
S
C250
S/W
U
D
R
S
2-phase 2-count
input
*4
C251
*1
H/W
*2
A
B
C252
S/W
A
B
R
C253
*1
H/W
*2
A
B
R
C253(OP)
*3
S/W
A
B
C254
S/W
A
B
R
S
C255
S/W
A
B
R
S