9.9.3
The start of the operation
1
Turn the power ON
Turn ON the power of the PLC.
When the power supply adapter or dedicated power supply is used, turn ON the power in the order
"Power supply adapter (or dedicated power supply)
→
PLC (built-in master)".
2
Confirming completion of the CONFIG mode
When collection of the remote I/O unit information is completed in the CONFIG mode, BFM #28
(1Ch) b4 turns ON.
Caution:
The ERR LED is lit while the power is ON in the CONFIG mode (DIP switch 6: ON, DIP switch 7: OFF), but it
does not indicate error.
3
Turn the power OFF
4
Setting the ONLINE mode
Set the DIP switch 6 to OFF and DIP switch 7 to OFF in the built-in master.
(For the switch setting, refer to the previous page.)
5
Turning ON the power again
Turn ON the power of the PLC. When the power supply adapter or dedicated power supply is used,
turn ON the power in the order "Power supply adapter (or dedicated power supply)
→
PLC (built-in
master)".