200
FX
3UC
Series Programmable Controllers
User’s Manual - Hardware Edition
7 Examples of Wiring for Various Uses
7.5 Ten Key Input [TKY (FNC 70)]
2. Input extension block
Example of program
Example of wiring
1) In the case of sink wiring
a) Sink only input type extension block
Use the sink only input, sink only output type main unit, a sink only input type input extension block.
The wiring example is the [FX
3UC
-32MT/D] + input extension block [FX
2NC
-16EX].
b) Sink/source common input type extension block
Use the sink/source common input, source only output type main unit, a sink/source common input
type input extension block.
The wiring example is the [FX
3UC
-32MT/DSS] + input extension block [FX
2NC
-16EX-DS].
2) In the case of source wiring
Use the sink/source common input, source only output type main unit, a sink/source common input type
input extension block.
The wiring example is the [FX
3UC
-32MT/DSS] + input extension block [FX
2NC
-16EX-DS].
TKY
M8000
X020 D100
M10
COM X020 X021 X022 X023
X025
X024
X026 X027
5
6
7
8
1
2
3
4
X030 X031
0
9
FX
2NC
-16EX
Fuse
24V DC Class D
grounding*
FX
3UC
-32MT/D
FX
3UC
-32MT-LT
Sink input
* The grounding resistance should be 100
Ω
or less.
+
-
+
-
COM0
X020 X021 X022 X023
X025
X024
X026 X027
5
6
7
8
1
2
3
4
X030 X031
0
9
Fuse
24V DC
Class D grounding*
FX
2NC
-16EX-DS
Sink input
FX
3UC
-32MT/DSS
* The grounding resistance should be 100
Ω
or less.
+
-
COM0
X020 X021 X022 X023
X025
X024
X026 X027
5
6
7
8
1
2
3
4
X030 X031
0
9
Fuse
24V DC Class D
grounding*
FX
2NC
-16EX-DS
Source input
FX
3UC
-32MT/DSS
* The grounding resistance should be 100
Ω
or less.
+
-