263
FX
3UC
Series Programmable Controllers
User’s Manual - Hardware Edition
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
9.6 Selection of the power supply for CC-Link/LT
1
O
utline
2
Exter
nal
D
im
en
sions
3
Ge
ne
ric
Speci
ficat
ions
4
Pow
er Suppl
y
Specif
icati
ons
5
Input
Spec
ific
ations
6
O
utput
Specif
icat
ions
7
Exam
pl
es
of
W
iri
ng
fo
r
Va
rious U
ses
8
Te
rm
inal B
lock
9
CC
-L
in
k/L
T
Ma
ste
r F
X
3UC
(LT
only)
10
D
ispl
ay m
odule
FX
3UC
(L
T only)
2. Rule when using power adapter or dedicated power supplies
When the capacity of the built-in power supply is insufficient, use the power supply adapter or dedicated
power supply in accordance with the system configuration. (The power supply adapter and dedicated power
supply can be used together.)
When using the power supply adapter or dedicated power supply, calculate "current consumption", "voltage
drop" and "minimum operating voltage (20.4V DC)" for each power supply adapter, and satisfy each condition
in the system configuration.
→
For the power supply adapter and dedicated power supply, refer to the manual of the
corresponding product.
System configuration examples
1) Current consumption calculation
2) Start-up current calculation
3) Voltage drop calculation
4) Confirmation related to the minimum operating voltage (20.4V DC) of the module
*1.
When using remote I/O stations that receive power for connected I/O equipment from the built-in
power supply, power supply adapter or dedicated power supply, include the current consumption of
the connected I/O equipment.
FX
3UC
-32MT-
LT
(Built-in
Built-in
power supply
(350mA)
Power adapter or
Dedicated power
supply
Power is
supplied.
LINK/POWER connector
LINK connector
Remote I/O
station c)
Remote I/O
station d)
Remote I/O
station g)
Remote I/O
station h)
Remote I/O
station e)
Remote I/O
station f)
Terminal
resistor
Remote I/O
station a)
Remote I/O
station b)
Power is supplied from Dedicated
power supply (1st module)
Power is supplied from Dedicated power
supply (2nd module)
Terminal
resistor
General-purpose
power supply
*1
*1. Used when dedicated power
supply is not required
=
Current consumption calculation in power adapter or
dedicated power supply (2nd module)
Current consumption calculation in built-in power supply
(1st module)
=
Total current consumption in remote I/O station
e) to h)
*1
Total current consumption in master station and
remote I/O station a) to d)
*1
Start-up current calculation supplied from built-in power
supply (1st module)
Start-up current calculation supplied from power adapter
or dedicated power supply (2nd module)
Total current of remote I/O station e) to h) at
start-up
*1
Total current of remote I/O station a) to d) at
start-up
*1
=
=
Voltage drop calculation supplied from built-
in power supply (1st module)
Calculate voltage drop in remote I/O station a) to d) based on
current consumption and distance to the furthest station.
Voltage drop calculation supplied from
power adapter or dedicated power supply
(2nd module)
Calculate voltage drop in remote I/O station e) to h) based on
current consumption and distance to the furthest station.
=
=
Minimum operating voltage (20.4V DC)
from power adapter (1st module)
=
Minimum operating voltage (20.4V DC)
from power adapter (2nd module)
=
Output voltage of power adapter or dedicated power supply
(2nd module) - voltage drop
≥
20.4V
Output voltage of built-in power supply (1st module)
- voltage drop
≥
20.4V